Note: This should be inspected by the maintenance
technician on a regular basis. Caution should always be
used as odorant may escape if the expansion tank has
been allowed to filled with odorant. Odorant fill of the
expansion tank is not a normal or recommended
operating condition.
Low Pressure Relief Adjustment
The overflow protector incorporates a low pressure relief
in the cap assembly for the purpose of maintaining the
maximum expansion tank pressure at 25 psi
(1.72 Bar).
To test and adjust follow these steps:
1. With valve V6 open,
figure 196, slowly open valve
V4,
figure 195, until gas begins discharging at
exhaust port.
2. Close valve V4 and see where pressure stabilizes
which should be 25 psi
(1.72 Bar).
3. If adjustment is needed:
a) First, loosen adjustment lock nut, located on top
of the overflow protector. To increase pressure
in the tank, turn the adjustment screw in, or to
the right. To lower pressure tank, turn the
adjustment screw out, or to the left.
b) Tighten lock nut.
c) Repeat until the desired pressure of 25 psi
(1.72 Bar) is obtained as described in in step 2
above.
Valve V4
Figure 195
Figure 227
Adjustment
lock nut
Adjustment screw
Valve V6