FRONT PANEL AND OPERATIONS   

 

1

  Upper display window 

2

  Lower display window 

3

 Set 

key 

4

  Data shift key (also for switching between 

manual/auto cyclic display)   

5

  Data decrease key (also for switch to 

display the previous channel) 

6

  Data increase key (also for switch to 

display the next channel) 

5

  10 LED indication lights.   

“MAN” on: Means manual circular display,   
“MAN” off: Means auto circular display.     
MIO, OP1, OP2, AL1, AL2, AU1, AU2 
indicate the input/output action of the 
corresponding module. “COM” on means communicating with the host computer. 

 

Basal operation description 

 
1. 

Switch display channel:

     

 

Press 

  to display next channel, and press 

  to display previous channel.    Press 

  can switch between auto cyclic display and manual display. 

 

2. 

Parameter setting: 

 

When the parameter lock is unlocked, press 

 and hold for about 2 seconds until 

parameter is displayed.  At this moment, press

 

in short

; all parameters will be 

displayed one by one.    When the parameters are set and the parameter lock is locked, 
press 

 can access Field Parameter Table.  The value of a parameter can be 

modified by

 or

.  Press 

  to go to next parameter.    Press 

 and hold 

can return to the previous parameter.  Press 

 + 

 can exit parameter setting 

status. 

   
3. 

Alarm display: 

 

The lower display window shows channel number. If high or low alarm occurs, the first 
digit from the left of lower display window will show “H” or “L”, and flickers, and if over 
range occurs (for example, wire broken for thermocouple input), the upper display 
window will show high or low limit valve, and the lower display window flickers.   
If only 2 input channels configured, then the upper and lower display window will show 
the input values of channel 1 and 2 respectively. When over range occurs, the 
corresponding display window will flickers.   

 

Lead wire resistance compensation for 2-wire RTD input:     
Offset value (parameter “Sc”) need to be set to counteract lead wire resistance for 2-wire 
type RTD like Pt100 or Cu50. This offset value can be set automatically by the following 
procedures: 

1.  Short connect 2 wiring terminals on the RTD sensor side 
2.  Set parameter “Loc” to 808, and then press 

 until “A” appears on the first digit of 

lower display window. 

MAN PRG 

COM 

MIO 

AL1  AL2 

OP1  OP2 

A/M 

RUN/HOLD 

AU2 

STOP 

AU1 

 

PV 

SV

AI 

Содержание AI-702M

Страница 1: ...l Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Provide accurate internal calculation fun...

Страница 2: ...sion 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows...

Страница 3: ...nsient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Ph...

Страница 4: ...that provides 24VDC power supply Connect to 4 20mA two wires transmitter z Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm i...

Страница 5: ...Response time 1 5 seconds if digital filter parameter is set as 0 or 1 z Automatic pilot time interval Approx 1 2s or 2s configurable z Alarm function High and low alarm configurable separately for e...

Страница 6: ...on Two wire RTD wiring RTD can select two wire or three wire method by B of AF parameter Two wire method enable to input two channel signals in one module but user has to measure and calculate the res...

Страница 7: ...ter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The l...

Страница 8: ...means no communication and no alarm it can be treated as normal z The light flashing with period 0 6 second means no communication and general error occurs z The light quickly flashing with period 0...

Страница 9: ...put spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re t...

Страница 10: ...IL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then t...

Страница 11: ...nction selection AF is used to select advanced function The value of AF is calculated as below AF Ax1 Bx2 Cx4 Dx8 Ex16 A 0 Slow cyclic display A 1 Fast cyclic display Above setting only affects displa...

Страница 12: ...ansmission current 0 220 Po Atmospheric pressure Defined atmospheric pressure when dry bulb wet bulb humidity measurement was activated Unit KPa 1 120 0 SPEd Wind speed Defined wind speed when dry bul...

Страница 13: ...AL1 L AL1 etc Parameters from EP1 to EP12 can define 12 field parameters at most if the number of field parameters is less than 12 sometimes even none it is necessary to define field parameters from...

Отзывы: