ALPx Alarm 

output 

From right side to left side, the first, second digit of AOP 
respectively indicate the alarm output assignment of H.AL, 
L.AL, as below: 

ALPx = 

_______ _______ 

L.AL H.AL 

 
Regarding to parameter value: 0 means no output. 
1,2,3,4,5,6,7 respectively indicate alarm output to OP1, 
OP2, AL1, AL2, AU1, AU2 and MIO. Shown as below: 

 L.AL 

H.AL 

No alarm 

OP1 1 

OP2 (L5 need) 

AL1 3 

AL2 (L5 need) 

AU1 5 

AU2 (L5 need) 

MIO 7 

For example:   
ALP1=43, low limit alarm (L.AL) of channel 1 output to AL2, 
ALP2=53, low limit alarm (L.AL) of channel 2 output to AU1, 
and both high limit alarms(H.AL) of both channel are sent to 
AL1. 

 

0~77 

Cn 

Number of 

input channels 

Define actual number of input channels.   
When Cn=2, the lower window display the present value of 
channel 2 instead of the channel number. 

702M: 0~ 2 
704M: 0~ 4 
706M: 0~ 6 

AF 

Advanced 

function 

selection 

AF is used to select advanced function.  The value of AF 
is calculated as below: 

AF=Ax1 + Bx2 + Cx4 + Dx8 + Ex16 

 

A=0, Slow cyclic display;   
A=1, Fast cyclic display.     
Above setting only affects display and has no effect on 
internal scan speed and alarm response time. 
B=0, RTD input use two-wire wiring;   
B=1, RTD input use three-wire wiring. 
C=0, Only channel 2 is retransmitted to COMM port;   
C=1, All input channels are cyclically retransmitted, and 
the retransmission time interval on every channel is about 
3 seconds.    The output range of all channels are defined 
by dIL2 and dIH2 only. 
D=0, Normal;   
D=1, All low limit alarms are changed to high limit alarm. 
E=0, Normal;   
E=1, Set M2(MIO) and M3(OUPT) support one channel 
input only.   
For example, to set a AI-702M with 2 inputs, slowly cyclic 
display, channel 1 input from three-wire RTD (J0 module 
on M1 socket), channel 2 input from thermocouple (J1 
module on M2 socket), current retransmission of channel 
2 outputted to COMM port, the AF parameter should be 
set as below:   
A=0,B=1,C=0,D=0, then AF=19. 

0~31 

Содержание AI-702M

Страница 1: ...l Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Provide accurate internal calculation fun...

Страница 2: ...sion 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows...

Страница 3: ...nsient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Ph...

Страница 4: ...that provides 24VDC power supply Connect to 4 20mA two wires transmitter z Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm i...

Страница 5: ...Response time 1 5 seconds if digital filter parameter is set as 0 or 1 z Automatic pilot time interval Approx 1 2s or 2s configurable z Alarm function High and low alarm configurable separately for e...

Страница 6: ...on Two wire RTD wiring RTD can select two wire or three wire method by B of AF parameter Two wire method enable to input two channel signals in one module but user has to measure and calculate the res...

Страница 7: ...ter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The l...

Страница 8: ...means no communication and no alarm it can be treated as normal z The light flashing with period 0 6 second means no communication and general error occurs z The light quickly flashing with period 0...

Страница 9: ...put spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re t...

Страница 10: ...IL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then t...

Страница 11: ...nction selection AF is used to select advanced function The value of AF is calculated as below AF Ax1 Bx2 Cx4 Dx8 Ex16 A 0 Slow cyclic display A 1 Fast cyclic display Above setting only affects displa...

Страница 12: ...ansmission current 0 220 Po Atmospheric pressure Defined atmospheric pressure when dry bulb wet bulb humidity measurement was activated Unit KPa 1 120 0 SPEd Wind speed Defined wind speed when dry bul...

Страница 13: ...AL1 L AL1 etc Parameters from EP1 to EP12 can define 12 field parameters at most if the number of field parameters is less than 12 sometimes even none it is necessary to define field parameters from...

Отзывы: