background image

dIPx 

Decimal point 

position 

dIPx is set to select display resolution for channel x 
for linear inputs, the corresponding display resolution of 
dIP=0,1,2,3 are 0, 0.0, 0.00 and 0.000   
for thermocouple or RTD inputs, when dIP=0, the display 
resolution is 1

; when dIP=1, the resolution is 0.1

Note: dIP only affects the display, and has no effect on 
internal data. 

0~3 

dILx 

Scale low limit 

dIL and dLH define the corresponding scale range of linear 
inputs such as mV, 0~5V, 1~5V, 0~10mA, 4~20mA. 
When the temperature input is retransmitted, dIL/dIH also 
defined the low/high limit of temperature. 
For example, a pressure transmitter transfers the pressure 
to standard 1~5V signal and sends to input channel 1. 
The input of 1V indicates the pressure=0, and 5V indicates 
the pressure=1MPa, and expected display resolution is 
0.001MPa.    Then the parameters should be set as below:
Sn1=33, dIP1=3, dIL1=0.000, dIH1=1.000 

-9990~+30000 

units or 0.1

 

dIHx 

Scale high limit 

Scx Input 

offset 

For thermocouple or three-wire RTD inputs, the units of Sc 
is 0.1

.  For example, when Sc=-100, the actual 

offset=-10

, then the measured temperature will be 10

 

lower than that when Sc=0. 
For two-wire RTD inputs, the actual offset = (Sc x signal 
unit).  The signal unit of Pt100 or 0~400ohm input is 
0.02ohm, and that of Cu50 or 0~240ohm input is 
0.012ohm.  For example, when Sc=-50, input type is 
Pt100, (-50 x 0.02ohm), then the actual offset= -1.     

-1999~+4000 
units or 0.1

 

dLx Digital 

filter 

The value of dF will determine the ability of filtering noise.   
dL=0, no filtering;   
dL=1, filtering with mean;   
dL=2~40, filtering with mean and integral. 
When a large value is set, the measurement input is 
stabilized but the response speed is slow.  Generally, it 
can be set to 1 to 3. 
If great interference exists, then you can increase 
parameter dF gradually to make momentary fluctuation of 
measured value less than 2 to 5.     
When the instrument is being metrological verified, dF can 
be set to 0 or 1 to shorten the response time.   

0~40 

Содержание AI-702M

Страница 1: ...l Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Provide accurate internal calculation fun...

Страница 2: ...sion 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows...

Страница 3: ...nsient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Ph...

Страница 4: ...that provides 24VDC power supply Connect to 4 20mA two wires transmitter z Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm i...

Страница 5: ...Response time 1 5 seconds if digital filter parameter is set as 0 or 1 z Automatic pilot time interval Approx 1 2s or 2s configurable z Alarm function High and low alarm configurable separately for e...

Страница 6: ...on Two wire RTD wiring RTD can select two wire or three wire method by B of AF parameter Two wire method enable to input two channel signals in one module but user has to measure and calculate the res...

Страница 7: ...ter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The l...

Страница 8: ...means no communication and no alarm it can be treated as normal z The light flashing with period 0 6 second means no communication and general error occurs z The light quickly flashing with period 0...

Страница 9: ...put spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re t...

Страница 10: ...IL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then t...

Страница 11: ...nction selection AF is used to select advanced function The value of AF is calculated as below AF Ax1 Bx2 Cx4 Dx8 Ex16 A 0 Slow cyclic display A 1 Fast cyclic display Above setting only affects displa...

Страница 12: ...ansmission current 0 220 Po Atmospheric pressure Defined atmospheric pressure when dry bulb wet bulb humidity measurement was activated Unit KPa 1 120 0 SPEd Wind speed Defined wind speed when dry bul...

Страница 13: ...AL1 L AL1 etc Parameters from EP1 to EP12 can define 12 field parameters at most if the number of field parameters is less than 12 sometimes even none it is necessary to define field parameters from...

Отзывы: