nonc
NO/NC
selection
Single channel relay module provides both normal open
and normal close output, while dual relay output module
only provides NO output.
If L5 dual real installed, set nonc=0, all in NO status, set
nonc=127, all in NC status.
However, by parameter “nonc”, the NO output can be
changed to NC output.
nonc = Ax1 + Bx2 + Cx4 + Dx8 + Ex16 + Fx32 + Gx64
A,B,C,D,E,F,G respectively set NO/NC output of OP1,
OP2, AL1, AL2, AU1, AU2 and MIO. 0 means the
corresponding output is NO, and 1 means NC output.
0 ~63, 127
OPn
Select the
channel to be
retransmitted
OPn=0, OUTP port is for alarm output.
OPn=1~6, OUTP port is used for retransmission of
channel OPn.
OPn=7, Compare with all channel, and retransmission the
maximum value’s channel to OUTP
OPn=8, Compare with all channel, and retransmission the
minimum value’s channel to OUTP
0~8
OPL
Low limit of
retransmission
current
When OUTP works as re-transmitter, OPL/OPH define the
low/high limit of re-transmisson. The unit is 0.1mA.
For example, to transmit the channel 1 input 0~600
℃
into
4~20mA output, the parameters should be set as below:
dIL1=0, dIH1=600, OPn=1, OPL=40, OPH=200
0~110
OPH
High limit of
retransmission
current
0~220
Po
Atmospheric
pressure
Defined atmospheric pressure, when dry bulb, wet bulb
humidity measurement was activated. Unit = KPa
1~120.0
SPEd Wind
speed
Defined wind speed, when dry bulb, wet bulb humidity
measurement was activated. Unit = m/S
0.01~10.00
Addr
Communication
address
Every instrument in the same communication line should
be assigned to different communication address. The
communication applies AIBUS protocol. Every input
channel takes one address. For example, if Cn=3 and
Addr=10, then the communication address 10~12 are
assigned to the instrument.
0 ~100
bAud Baud
rate
When COMM module interface is used for communication,
bAud defines the baud rate with range 300~19200bit/s.
When linear current output module is installed in COMM
socket, and bAud is set to 0~220, the COMM output can
work as retransmission output. It can retransmit channel
2 input or cyclically retransmit all input channels into linear
current. bAud defines the output high limit, and Addr
defines the low limit. The unit is 0.1mA. For example,
to output 4~20mA current, Addr should be set to 40, and
bAud=200.
0 ~19.2K
Loc Parameter
lock
Loc=0, Allow to display and modify the field parameters,
which is defined in EP1~EP12.
Loc=1, Can display the field parameters, but can’t modify
them.
Loc=808, Allow to display and set all parameters.
0 ~9999