17

2.3.3 Auto Tuning

When AI control method is chosen (CtrL=APId / nPId), the PID parameters can be obtained by

running auto-tuning.

In basal display status, press

for 2 seconds, the

At

parameter will appear.Press

to

change the value of

At

from

oFF

to

on

,then press

to active the auto-tuning

process.During auto tuning,the instrument executes on-off control.After 2-3 times of on-off

action,the instrument will obtain the optimal control parameter

value.

If you want to escape from auto tuning status, press and hold the key for about 2 seconds until the

"At" parameter appear again. Change

At

from

on

to

oFF

, press to confirm, then the

auto tuning processwill be cancelled. (P.S. If parameter

SPr

activate and the heating was

running, then will stop the

At

until completed the heat up process. ) If the controller was applied

on heat/cooling duel output system, PID parameter need separate two group to process auto tuning.

When the controller was cooling control from AUX, this time can enable auto tuning to obtain P2, I2,

d2.

Note 1:

At AI-516P, when auto tuning was running, the program timer will stop until tuning finish.

Note 2:

If the setpoint is different, the parameters obtained from auto-tuning are possible different. So you

d better set setpoint to an often-used value or middle value first, and then start auto-tuning. For the

ovens with good heat preservation, the setpoint can be set at the highest applicable temperature.

Depending on the system, the auto-tuning time can be from several seconds to several hours.

Note 3:

Parameter CHYS (on-off differential, control hysteresis) has influence on the accuracy of

auto-tuning. Generally, smaller value of CHYS, will get higher precision of auto tuning result. Too

large value of CHYS, will made the controller out of control, so, CHYS is recommended to be 2.0.

Note 4:

AI series instrument has the function of self-adaptation. It is able to learn the process while working.

He control effect at the first run after auto tuning is probably not perfect, but excellent control result

will be obtained after a period of time because of self-adaptation.

3. PARAMETERS AND SETTINGS

3.1 Parameter Lock (Loc) and Field Parameters

Parameter was protected by LOC (Parameter LOCK) to prevent setting error. The function was

shown as below:

: allow to modify data or execute

X : not allow to modify data or execute

Run, Stop, Hold. and Program Time & Temp. function just for AI-516P only

Содержание AI-516

Страница 1: ...AI 516P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Applicable for accurate controls of Temperature Pressure Flow Level and Humidity etc Operation Instruction ver 8 2 Web www rievtech com Tel 86 25...

Страница 2: ...r Setting Flow Chart 15 2 3 Operation Description 15 2 3 1 Parameter Setting 15 2 3 2 Set Value Setting 15 2 3 3 Auto Tuning 17 3 2 The Parameter Table 18 3 3 Additional Remarks of Special Functions 2...

Страница 3: ...ss level of quality anti interference ability and safety POINTS FOR ATTENTION This manual is AI 516 AI 516P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Version 8 2 Certain functions in this manual a...

Страница 4: ...ront panel dimension A A2 Front panel 96 96mm width height cut out 92 92mm depth behind mounting surface 100mm A2 has a light bar with 25 segments and 4 levels of luminosity B Front panel 160 80mm wid...

Страница 5: ...the inside of the instrument can fix it If not send the instrument back to the factory to examine and repair 1 3 Modules 1 3 1 Slots of modules AI 516 516P series instruments have five slots for modu...

Страница 6: ...normally open relay output module large volume Capacity 30VDC 2A 250VAC 2A W1 W2 TRIAC no contact normally open W2 is normally close discrete output module Capacity 100 240VAC 0 2A G SSR voltage outp...

Страница 7: ...current output all need the 12V power supply If more than one of the above modules are installed in order to be electric isolated only one of them can be module without electric isolation the other m...

Страница 8: ...1 4 TECHNICAL SPECIFICATION Input type Either of below specifications can be used selectively in the one instrument Thermocouple K S R E J N T B WRe3 WRe25 WRe5 WRe26 Resistance temperature detector...

Страница 9: ...r module Linear current output 0 20mA 4 20mA can scaling by user Output voltage X3 10 5V X5 7V maximum load resistor 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according...

Страница 10: ...inputted from terminals 16 and 14 Note 3 The compensation wires for different kinds of thermocouple are different and should be directly connect to the terminals When the internal auto compensation mo...

Страница 11: ...V signal can be converted to 0 500mV or 100 500mV by connecting external precise resistors 4 20mA can be converted to 100 500mV by connecting a 25ohm resistor then be inputted from terminals 9 and 8 N...

Страница 12: ...ing graph of instruments with D5 dimension as below Note D5 dimension din rail mounting instruments have one channel alarming and communication function main output slot can install G X3 X5 K1 K5 L1 m...

Страница 13: ...TIONS 2 1 Front Panel Description Upper display window Displays PV parameter code etc Lower display window Displays SV parameter value oralarm message Setup key For accessing parameter table and confo...

Страница 14: ...he set point SV This status is called basic display status Symbol description was shown as following table Note 1 The alarm message can turn off by setting parameter AdIS to oFF Note 2 When occur orAL...

Страница 15: ...don t release and then press key simultaneously can escape from the parameter table The instrument will escape auomatically from the parameter table if no key is pressed within 25 seconds and the chan...

Страница 16: ...toP is alternately displayed on the lower window and hold the key for about 2 seconds until the lower display window displays the Run symbol instrument then will start the program If parameter PAF set...

Страница 17: ...uning finish Note 2 If the setpoint is different the parameters obtained from auto tuning are possible different So you d better set setpoint to an often used value or middle value first and then star...

Страница 18: ...2 LoAL EP3 HdAL EP4 LdAL EP5 nonE EP6 nonE EP7 nonE EP8 nonE and Loc 0 You can redefine field parameters and Loc to change operation style For example you can execute auto tuning from field parameter...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...uction angle of thyristor With non linear power adjustment according to the characters of sine wave it can get ideal control The trigger adopts self synchronizing technology so it can also work even w...

Страница 24: ...ed control system software developed by Rievtech can control and manage 1 160 AI instruments record the data generate and print reports If users want to develop their own distributed control system by...

Страница 25: ...orrect code has a high accuracy as high as 30000 times than parity check can promise the reliable data Under most conditions AI controllers are not influenced by other brand s product communication No...

Страница 26: ...ary number Return data writing or reading whichever below 10 bit data is returned PV SV MV and alarm status writing reading parameter value correct code Thereinto PV SV and reading values each takes u...

Страница 27: ...27...

Страница 28: ...127 for high value if read integer which is 32512 32767 because maximum set range is 32000 parameter beyond 32512 means the mark for mis reading parameter code and is to be processed in the computer p...

Страница 29: ...orresponding parameters are set as below When CtrL POP PV is retransmitted to linear current the instrument works as temperature re transmitter When CtrL SOP SV is transmitted and outputted and the in...

Страница 30: ...program will stop automatically Power cut resume event handling There are 5 events handling method selectable for power resume after power cut off Please refer to parameter PonP PV startup and PV prep...

Страница 31: ...en reached Temperature B SP 2 The unit of temperature set is and the unit of time set is minute The following example includes 5 steps which is linear temperature heating up constant temperature linea...

Страница 32: ...m stops and switches to stop status Set t xx 0 1 122 0 Negative value of this range represents a jump operation which will jump to step xx and event output Range 1 120 is for step jumping application...

Страница 33: ...the StEP will be automatically set to1 Thus if StEP is not change to other value a program will start from step1 If multiple curves are defined the control can jump to different curve by setting step...

Отзывы: