background image

30

4.1 Concepts and functions Program

StEP

The No. of the program Step can be defined from 1 to 30, and the current Step is the program Step

being executing.

StEP time

Total run time of the program step. The unit is minute and the available value range from 0.1 to

3200.

R

unning time The Time of current Step has run. As the running time reaches the Step time, the

program will jump to the next Step automatically.

Jump

The program can jump to any other steps in the range of 1 to 30 automatically as you programmed

in the program Step,and realize cycle control.

Run/Hold

When program is in the running status, timer works, and set point value changes according to the

preset curve. When program is in the holding status, timer stops, and set point remains to make

temperature hold also. The holding operation can be programmed into the program step.

Stop

When the stop operation is activated, the program will stop, running time will be clear, event output

switch will reset and the output control will stop output. If run operation is activated when instrument

is in the stop status, the program will start-up and run again from the set step no. The stop function

can be programmed into the program Step. The stop operation can also be performed manually at

any time. (After stop operation is done, the step no. will be set to 1, but user can modify it again). If

the program ran the last step of

Pno

, program will stop automatically.

Power cut/resume event handling

There are 5 events handling method selectable for power resume after power cut off. Please refer

to parameter PonP.

PV startup and PV preparation function (rdy function)

At the beginning of starting a program, resuming a program after power cut or continuing to run a

program after it is just

modified, the PV (process value) are often quite different from the set point. PV startup function and

PV preparation

function can make PV and set point consistent, and avoid unexpected result. When PV startup

function enabled, the instrument will adjust the running time automatically to make the expected set

point is the same as the current PV.

For example, the program is set that the temperature will be raised from 25

to 625

in 600

minutes. But the current PV is 100

, then the instrument will automatically to run this program start

from 75 minutes, that mean changed the temperature raised from 100

to 625

in 525 minutes

(600-75) min.

At the above situation(PV=100, SV=25, first step SV), when PV preparation function is enable, the

alarm function will be blocked at that time, and PV will be adjusted to approach SV until the

deviation alarm condition is released (PV is between SV-LdAL and SV+HdAL). After deviation

alarm was off, the controller starts to run the program again.

Preparation function (rdy Function) is helpful to keep the integrity of the program, but it will prolong

the program time because the start of the program is postponed.

PV startup function is prior to PV preparation function. If both function are enabled, the system

Содержание AI-516

Страница 1: ...AI 516P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Applicable for accurate controls of Temperature Pressure Flow Level and Humidity etc Operation Instruction ver 8 2 Web www rievtech com Tel 86 25...

Страница 2: ...r Setting Flow Chart 15 2 3 Operation Description 15 2 3 1 Parameter Setting 15 2 3 2 Set Value Setting 15 2 3 3 Auto Tuning 17 3 2 The Parameter Table 18 3 3 Additional Remarks of Special Functions 2...

Страница 3: ...ss level of quality anti interference ability and safety POINTS FOR ATTENTION This manual is AI 516 AI 516P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER Version 8 2 Certain functions in this manual a...

Страница 4: ...ront panel dimension A A2 Front panel 96 96mm width height cut out 92 92mm depth behind mounting surface 100mm A2 has a light bar with 25 segments and 4 levels of luminosity B Front panel 160 80mm wid...

Страница 5: ...the inside of the instrument can fix it If not send the instrument back to the factory to examine and repair 1 3 Modules 1 3 1 Slots of modules AI 516 516P series instruments have five slots for modu...

Страница 6: ...normally open relay output module large volume Capacity 30VDC 2A 250VAC 2A W1 W2 TRIAC no contact normally open W2 is normally close discrete output module Capacity 100 240VAC 0 2A G SSR voltage outp...

Страница 7: ...current output all need the 12V power supply If more than one of the above modules are installed in order to be electric isolated only one of them can be module without electric isolation the other m...

Страница 8: ...1 4 TECHNICAL SPECIFICATION Input type Either of below specifications can be used selectively in the one instrument Thermocouple K S R E J N T B WRe3 WRe25 WRe5 WRe26 Resistance temperature detector...

Страница 9: ...r module Linear current output 0 20mA 4 20mA can scaling by user Output voltage X3 10 5V X5 7V maximum load resistor 500ohm output precision 0 2 FS Electromagnetic compatibility EMC 4KV 5KHz according...

Страница 10: ...inputted from terminals 16 and 14 Note 3 The compensation wires for different kinds of thermocouple are different and should be directly connect to the terminals When the internal auto compensation mo...

Страница 11: ...V signal can be converted to 0 500mV or 100 500mV by connecting external precise resistors 4 20mA can be converted to 100 500mV by connecting a 25ohm resistor then be inputted from terminals 9 and 8 N...

Страница 12: ...ing graph of instruments with D5 dimension as below Note D5 dimension din rail mounting instruments have one channel alarming and communication function main output slot can install G X3 X5 K1 K5 L1 m...

Страница 13: ...TIONS 2 1 Front Panel Description Upper display window Displays PV parameter code etc Lower display window Displays SV parameter value oralarm message Setup key For accessing parameter table and confo...

Страница 14: ...he set point SV This status is called basic display status Symbol description was shown as following table Note 1 The alarm message can turn off by setting parameter AdIS to oFF Note 2 When occur orAL...

Страница 15: ...don t release and then press key simultaneously can escape from the parameter table The instrument will escape auomatically from the parameter table if no key is pressed within 25 seconds and the chan...

Страница 16: ...toP is alternately displayed on the lower window and hold the key for about 2 seconds until the lower display window displays the Run symbol instrument then will start the program If parameter PAF set...

Страница 17: ...uning finish Note 2 If the setpoint is different the parameters obtained from auto tuning are possible different So you d better set setpoint to an often used value or middle value first and then star...

Страница 18: ...2 LoAL EP3 HdAL EP4 LdAL EP5 nonE EP6 nonE EP7 nonE EP8 nonE and Loc 0 You can redefine field parameters and Loc to change operation style For example you can execute auto tuning from field parameter...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...uction angle of thyristor With non linear power adjustment according to the characters of sine wave it can get ideal control The trigger adopts self synchronizing technology so it can also work even w...

Страница 24: ...ed control system software developed by Rievtech can control and manage 1 160 AI instruments record the data generate and print reports If users want to develop their own distributed control system by...

Страница 25: ...orrect code has a high accuracy as high as 30000 times than parity check can promise the reliable data Under most conditions AI controllers are not influenced by other brand s product communication No...

Страница 26: ...ary number Return data writing or reading whichever below 10 bit data is returned PV SV MV and alarm status writing reading parameter value correct code Thereinto PV SV and reading values each takes u...

Страница 27: ...27...

Страница 28: ...127 for high value if read integer which is 32512 32767 because maximum set range is 32000 parameter beyond 32512 means the mark for mis reading parameter code and is to be processed in the computer p...

Страница 29: ...orresponding parameters are set as below When CtrL POP PV is retransmitted to linear current the instrument works as temperature re transmitter When CtrL SOP SV is transmitted and outputted and the in...

Страница 30: ...program will stop automatically Power cut resume event handling There are 5 events handling method selectable for power resume after power cut off Please refer to parameter PonP PV startup and PV prep...

Страница 31: ...en reached Temperature B SP 2 The unit of temperature set is and the unit of time set is minute The following example includes 5 steps which is linear temperature heating up constant temperature linea...

Страница 32: ...m stops and switches to stop status Set t xx 0 1 122 0 Negative value of this range represents a jump operation which will jump to step xx and event output Range 1 120 is for step jumping application...

Страница 33: ...the StEP will be automatically set to1 Thus if StEP is not change to other value a program will start from step1 If multiple curves are defined the control can jump to different curve by setting step...

Отзывы: