10
Note 1:
For linear voltage input, if the range is below 500mV,connect to terminals 19 and 18. 0
~
5V or 1
~
5V signal canbe inputted from terminals 17 and 18.
Note 2:
4
~
20mA linear current signal can change to 1
~
5V voltage signal by connecting a 250 ohm
resistor, and then be inputted from terminals 17 and 18. If I4 module is installed in MIO slot, 4
~
20mA signal can be inputted from terminals 14+ and 15-, and 2-wire transmitter can be inputted
from terminals 16+ and 14-.
Note 3:
The compensation wires for different kinds of thermocouple are different, and should be
directly connect to the terminals. When the internal auto compensation mode is used, connecting
the common wire between the compensation wire and the terminals will cause measurement error.
Note 4:
When main output selected linear current or SSR voltage, output form terminal 13+, 11-,
Wiring graph of D dimension instruments (72×72mm)
Note 1:
Linear voltage signal of range below 500mV should be inputted from terminals 13 and 12, and
signal of 0
~
5V and 1
~
5V should be inputted from terminals 11 and 12.
Note 2: