5167821-YTG-K-1118
Johnson Controls Ducted Systems
73
75°F
85°F
3125
77
71.4
5.3
-
-
-
-
-
-
66.4
5.7
-
-
-
-
-
-
72
65.9
5.1
10.5
7.5
4.6
1.6
-
-
61.0
5.5
9.2
6.6
4.0
1.5
-
-
67
60.3
5.0
25.8
22.9
19.9
17.0
14.0
-
55.6
5.4
20.9
18.3
15.8
13.2
10.6
-
62
57.9
5.0
38.1
33.3
30.3
27.4
24.4
21.5
53.4
5.3
29.7
25.0
22.4
19.9
17.3
14.7
3750
77
74.1
5.2
-
-
-
-
-
-
69.6
5.6
-
-
-
-
-
-
72 68.3
5.1
13.4
9.7
6.0
2.3
-
-
63.9
5.5
12.8
9.3
5.7
2.2
-
-
67 62.6
5.0
33.3
29.6
25.9
22.2
18.5
-
58.2
5.3
29.9
26.4
22.9
19.4
15.9
-
62 60.1
4.9
46.9
43.1
39.4
35.7
32.0
28.3
56.0
5.3
40.1
36.6
33.1
29.6
26.1
22.6
57 58.4
4.9
48.6
44.9
41.2
37.5
33.7
30.0
54.9
5.3
41.6
38.0
34.5
31.0
27.5
24.0
4375
77
76.8
5.2
-
-
-
-
-
-
72.8
5.6
-
-
-
-
-
-
72 70.8
5.1
16.3
11.8
7.3
2.9
-
-
66.8
5.4
16.3
11.9
7.4
3.0
-
-
67 64.9
4.9
40.9
36.4
31.9
27.4
23.0
-
60.9
5.3
38.9
34.5
30.0
25.6
21.1
-
62 62.3
4.9
55.7
53.0
48.5
44.1
39.6
35.1
58.5
5.2
50.6
48.2
43.8
39.3
34.9
30.4
57 60.5
4.9
55.6
53.8
50.7
46.2
41.7
37.2
57.4
5.3
50.7
49.0
45.7
41.2
36.8
32.3
5000
77
79.5
5.2
-
-
-
-
-
-
75.9
5.5
-
-
-
-
-
-
72 73.3
5.0
19.2
14.0
8.7
3.5
-
-
69.7
5.4
19.9
14.5
9.1
3.8
-
-
67 67.2
4.9
48.4
43.1
37.9
32.6
27.4
-
63.5
5.2
47.9
42.5
37.2
31.8
26.4
-
62 64.5
4.8
64.5
62.9
57.6
52.4
47.2
41.9
61.1
5.2
61.1
59.8
54.4
49.1
43.7
38.3
57 62.6
4.8
62.6
62.6
60.2
54.9
49.7
44.5
59.9
5.2
59.9
59.9
56.8
51.4
46.0
40.7
5250
72 73.1
5.0
20.0
14.5
9.1
3.6
-
-
69.1
5.3
20.6
15.0
9.4
3.9
-
-
67 67.0
4.9
50.2
44.8
39.3
33.8
28.4
-
62.9
5.2
49.5
43.9
38.3
32.8
27.2
-
62 64.3
4.8
64.3
63.5
59.8
54.3
48.9
43.4
60.5
5.2
60.5
59.9
56.1
50.5
45.0
39.4
57 62.4
4.8
62.4
62.4
61.2
55.7
50.3
44.8
59.3
5.2
59.3
59.3
57.8
52.2
46.6
41.1
5500
72 72.9
5.0
20.8
15.1
9.4
3.7
-
-
68.4
5.3
21.3
15.5
9.7
4.0
-
-
67 66.7
4.8
52.1
46.4
40.7
35.0
29.3
-
62.3
5.2
51.0
45.3
39.5
33.7
28.0
-
62 64.1
4.8
64.1
64.1
61.9
56.3
50.6
44.9
59.9
5.1
59.9
59.9
57.8
52.0
46.2
40.5
57 62.2
4.8
62.2
62.2
62.2
56.5
50.9
45.2
58.8
5.1
58.8
58.8
58.8
53.0
47.2
41.5
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBh = 3.415 x kW. Refer to the appropriate blower
performance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
ZT150 (12.5 ton) reheat (continued)
Air on evaporator
coil
Temperature of air on condenser coil
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
Total
capacity
1
(MBh)
Total input
(kW)
2
Sensible capacity (MBh)
CFM
WB
(°F)
Return dry bulb (°F)
Return dry bulb (°F)
90
85
80
75
70
65
90
85
80
75
70
65
Содержание ZT SERIES