![York ZT SERIES Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/york/zt-series/zt-series_technical-manual_3878171101.webp)
5167821-YTG-K-1118
Johnson Controls Ducted Systems
101
Unit description/model
ZT090
Test configuration
Horizontal (side supply) ducted discharge
External static pressure (IWG)
0.4
1.0
1.6
2.0
Nominal airflow (CFM)
3000
2800
2600
2400
Octave band center frequency
(Hz)
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
63
84
86
89
90
125
80
82
84
86
250
73
75
77
79
500
67
68
69
71
1000
64
66
68
70
2000
62
64
66
68
4000
60
63
65
67
8000
53
56
58
60
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings
Unit description/model
ZT102
Test configuration
Horizontal (side supply) ducted discharge
External static pressure (IWG)
0.4
1.0
1.6
2.0
Nominal airflow (CFM)
3400
3200
3000
2800
Octave band center frequency
(Hz)
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
Full stage cooling operation
(dB)
1
63
87
89
90
91
125
81
83
85
86
250
75
76
79
81
500
70
70
73
75
1000
68
69
72
74
2000
66
67
70
72
4000
64
65
68
71
8000
58
59
63
65
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings