5167821-YTG-K-1118
20
Johnson Controls Ducted Systems
Condenser fan data
Quantity of fans
4
4
4
4
4
Fan diameter (inches)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Quantity of motors
4
4
4
4
4
Motor HP each
1/3
1/3
1/3
1/3
1/3
No. of speeds
2
2
2
2
2
1st speed/2nd speed RPM
850/600
850/600
850/700
850/700
900/700
1st speed/2nd speed total CFM
14000/9500
14000/9500
14000/11000
14000/11000
15000/11000
Belt drive evap. fan data
Quantity
1
1
1
1
1
Fan size (inches)
15 x 15
15 x 15
15 x 15
15 x 15
15 x 15
Type
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor sheave
1VL40
1VM50
1VL40
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower sheave
AK74
AK74
AK69
AK69
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A53
A54
A52
A54
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
56
56
56
184T
Filters
Quantity - size
4 - (24 x 20 x 2)
5,6
4 - (24 x 20 x 2
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 2)
5, 6
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
4 - (24 x 20 x 4)
7
1. Gas units
2. Cooling only, electric
3. 1st stage 60% of 2nd stage
4. ZT078, ZT090, ZT102, ZT120, and ZT150 have crankcase heaters as standard.
5. 2 in. throwaway, standard, MERV (Minimum Efficiency Reporting Value) 3.
6. 2 in. pleated, optional, MERV 8.
7. 4 in. pleated, optional, MERV 13.
ZT078-150 physical data (continued)
Component
Models
ZT078
ZT090
ZT102
ZT120
ZT150
Nominal tonnage
6.5
7.5
8.5
10
12.5
Содержание ZT SERIES
Страница 131: ...5167821 YTG K 1118 Johnson Controls Ducted Systems 131 Typical CPC BAS control wiring diagram...
Страница 132: ...5167821 YTG K 1118 132 Johnson Controls Ducted Systems Typical HONEYWELL BAS control wiring diagram...
Страница 133: ...5167821 YTG K 1118 Johnson Controls Ducted Systems 133 Typical NOVAR BAS control wiring diagram...