FORM 160.81-O1 (1020)
ISSUE DATE 10/05/2020
81
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW™ CONTROL CENTER
2
SLOT
NO.
DESCRIPTION
2308 Motor: Current Limit Local Setpoint
2309 Motor: Current Limit Remote Analog Setpoint
2310 Motor: Current Limit Remote ISN Setpoint
2311 Motor: Current Limit Remote Modem Setpoint
2312 Motor: Current Limit Selected Setpoint
2313 Motor: Pulldown Demand Time Remaining
2314 Motor: Pulldown Demand Limit Setpoint
2315 Motor: Pulldown Demand Time Setpoint
2316 Motor: Anti-Recycle Time Remaining
2317 Motor: Current Limit Remote Digital Setpoint
Mod “B” SSS Only
2570 Serial SSS: Input Power
2571 Serial SSS: Kilowatt Hours
2572 Serial SSS: Phase A Current
2573 Serial SSS: Phase B Current
2574 Serial SSS: Phase C Current
2575 Serial SSS: Phase A Voltage
2576 Serial SSS: Phase B Voltage
2577 Serial SSS: Phase C Voltage
2578 Serial SSS: Phase A Temperature
2579 Serial SSS: Phase B Temperature
2580 Serial SSS: Phase C Temperature
2581 Serial SSS: Starter Model
2582 Serial SSS: Full Load Amps
2583 Serial SSS: Voltage Range
2584 Serial SSS: Starting Current
SLOT
NO.
DESCRIPTION
2585 Serial SSS: Is Serial Communications OK
2586 Serial SSS: Panel to SSS Comm Errors
2587 Serial SSS: to Panel Comm Errors
8206 Refrigerant Level: Position
8207 Refrigerant Level: Is Valve Closing
8208 Refrigerant Level: Is Valve Opening
16401 Oil: Pressure
16402 Oil: Differential Pressure
(Oil Pressure – Evaporator Pressure)
16407 Oil: Differential Filter Pressure
(Discharge Pressure – Oil Pressure)
16415 Hot Gas Bypass: Is Solenoid On
17409 Liquid Injection: Is Solenoid On