JOHNSON CONTROLS
22
FORM 160.81-O1 (1020)
ISSUE DATE 10/05/2020
SECTION 2 - OPTIVIEW™ CONTROL CENTER
Optiview Control Center
Notes:
1. Saturation temperatures are calculated values. They are derived from applicable refrigerant pressure-temperature conversion lookup table
in the program. They will display XXX if the pressure used for the calculation is out of range.
2. Style B (and later) chillers are not equipped with an Evaporator Refrigerant Temperature Sensor (RT7). Software versions C.MLM.05.04.
xxx (and later) do not read or display this value.
ANALOG INPUT
ENGLISH RANGE
METRIC RANGE
LOW
HIGH
UNITS
LOW
HIGH
UNITS
Leaving Chilled Liquid Temperature
0.0
82.0
°F
-17.7
27.7
°C
Return Chilled Liquid Temperature
0.0
94.1
°F
-17.7
34.5
°C
Leaving Condenser Liquid Temperature
8.0
133.5
°F
-13.3
56.3
°C
Return Condenser Liquid Temperature
8.0
133.5
°F
-13.3
56.3
°C
Evaporator Refrigerant Temperature (note 2)
0.0
126.1
°F
-17.7
52.3
°C
Discharge Temperature
31.8
226.3
°F
-0.1
107.9
°C
Condenser Pressure
0.0
315.0
PSIG
0.0
2172.4
KPAG
Discharge Pressure
0.0
315.0
PSIG
0.0
2172.4
KPAG
Drop Leg Refrigerant Temperature
0.0
121.7
°F
-17.7
49.8
°C
Refrigerant Level
0.0
100.0
%
0.0
100.0
%
Condenser Saturation Temperature (note 1)
-98.7
160.1
°F
-72.6
71.7
°C
Evaporator Pressure
5.5
77.4
PSIG
37.9
533.7
KPAG
Evaporator Saturation Temperature (note 1)
-44.9
64.7
°F
-42.7
18.1
°C
Oil Pressure
0.0
315.0
PSIG
0.0
2172.4
KPAG
Languages
The Screens can be displayed in various languages.
Language selection is done on the USER screen. The
desired language is selected from those available.
Not all languages are available. English is the default
language. If a language other than English is being
displayed, an English-only speaking person should
navigate to the USER screen using the preceding Navi-
gation chart and select English per the USER screen
instructions in this book.
Analog Input Ranges
The following table indicates the valid display range
for each of the analog input values. In the event that the
input sensor is reading a value outside of these ranges,
the < or > symbols will be displayed beside the mini-
mum or maximum value, respectively.