JOHNSON CONTROLS
98
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 5 – TECHNICAL DATA
TWELVE FAN UNITS
DIMENSIONS – YLAA0200HE, YLAA0230HE
035-24059-017 REV-
LD26943
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
CONTROL PANEL BOTTOM DETAIL
20.7 [0.81]
1177 [46.35]
5” VICTAULIC
INLET
5” VICTAULIC
OUTLET
137.5
[5.43]
5” VICTAULIC INLET
5” VICTAULIC OUTLET
2938.4 [115.69]
3” VICTAULIC OUTLET
3” VICTAULIC OUTLET
588.3
[23.16]
6968.9 [274.37] - FRAME LENGTH
7006.0 [275.83] - OVERALL LENGTH
4986.1 [196.30]
6459.3 [254.30]
3154.3 [124.18]
2061.5 [81.16]
1256.1 [49.45]
411.
4
[16.20]
1275.7 [50.22]
1085.1 [42.72]
732.9 [28.85] 685.
7
[27.00]
(OPTIONAL HEAT
RECOVERY UNIT)
2241.5 [88.25] - FRAME WIDTH
2253.344 [88.71]
OVERALL WIDTH
FRAME HEIGH
T
2251.4 [88.64]
2397.7 [94.40]
1611.6 [63.45]
1305.1 [51.38]
1839.5 [72.42]
1753.2 [69.03]
194.6 [7.66]
36.
4
[1.43]
ORIGIN
80.
3
[3.16]
2077.
3
[81.78]
15.9mm [5/8”] DIA
MOUNTING HOLES (TYP.)
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
FIGURE 33 -
TWELVE FAN UNITS DIMENSIONS - YLAA200HE, YLAA0230HE
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...