![York YLAA0041 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/york/ylaa0041/ylaa0041_manual_4227837041.webp)
JOHNSON CONTROLS
41
SECTION 4 – INSTALLATION
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
4
FIGURE 11 -
SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT
SWITCH OR CIRCUIT BREAKER
SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED
DISCONNECT SWITCH OR CIRCUIT BREAKER
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
before working on equipment.
The unit evaporator heater uses 120 VAC.
Disconnecting 120 VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
Power Panel
Control Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L1 1L2 1L3
G
R
D
MICROPANEL
Flow Switch
See electrical note 9
Power Panel
Control Panel
Power Panel
Control Panel
Terminal Block,
NF Disconnect SW
or Circuit Breaker
1L1 1L2 1L3
1L1 1L2 1L3
G
R
D
G
R
D
G
R
D
MICROPANEL
2
L
XTBC2
XTBC1
13
14
Flow Switch
See electrical note 9
Field
Provided
Unit Power
Supply
Field Provided 120-1-60
Micropanel Power Supply if
Control Transformer not supplied.
Field supplied control power wiring
must be run in separate grounded
conduit. Never run control wiring
in the same conduit with power
wiring.
LD13141
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...