SECTION 8 – UNIT OPERATION
TABLE 26 -
YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (5
OR 6 FANS PER SYSTEM)
FAN
STAGE
ON*
OFF**
IPUII I/O OUTPUT
FAN CONTACTOR
FAN #
SYS 1
SYS 2
SYS 1
SYS 2
SYS 1
SYS 2
1
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE
TB7-8
TB10-8
1-KF1
2-KF1
1-MF1
2-MF1
2
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE
AND FAN STAGE
1 IS ENERGIZED
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE
AND FAN
STAGE 1 IS
ENERGIZED
TB7-8
and
TB7-9
TB10-8
and
TB10-9
1-KF1
and
1-KF2
2-KF1
and
2-KF2
1-MF1
and
1-MF2
and
1-MF3
2-MF1
and
2-MF2
and
2-MF3
3
DP >
PROGRAMMED
FAN CONTROL
ON PRESSURE
AND FAN
STAGES 1 AND 2
ARE ENERGIZED
DP <
PROGRAMMED
FAN CONTROL
ON PRESSURE
MINUS
PROGRAMMED
DIFFERENTIAL
PRESSURE
AND FAN
STAGES 1
AND 2 ARE
ENERGIZED
TB7-8
and
TB7-9
and
TB7-10
TB10-8
and
TB10-9
and
TB10-10
1-KF1
and
1-KF2
and
1-KF3
2-KF1
and
2-KF2
and
2-KF3
5 FAN:
1-MF1
and
1-MF2
and
1-MF3
and
1-MF4
and
1-MF5
6 FAN:
1-MF1
and
1-MF2
and
1-MF3
and
1-MF4
and
1-MF5
and
1-MF6
5 FAN:
1-MF1
and
1-MF2
and
1-MF3
and
1-MF4
and
1-MF5
6 FAN:
1-MF1
and
1-MF2
and
1-MF3
and
1-MF4
and
1-MF5
and
1-MF6
* When a fan stage is turned on, the pressure for the next stage is increased 20 psig and ramped back to the programmed on pressure over
the next 20 seconds.
** When a fan stage is turned off (Programmed ON pressure minus the differential), the OFF pressure for the next stage is decreased 20 psig
and ramped back to the programmed OFF pressure minus the differential.
The time delay (fan delay timer) between
turning fan stages on and off is fixed at
5 seconds.
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...