![York YLAA0041 Скачать руководство пользователя страница 116](http://html1.mh-extra.com/html/york/ylaa0041/ylaa0041_manual_4227837116.webp)
JOHNSON CONTROLS
116
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
SECTION 6 – COMMISSIONING
Leave all other settings not listed in the following table in their default values.
TABLE 13 -
DRIVE PROGRAMMING PARAMETERS
PARAMETER CODE
DESCRIPTION
SETTING
9902
Function Select
0
9905
Motor Rated Voltage
See motor nameplate
(208 V, 230 V, 460 V)
9906
Motor Rated Current
See motor nameplate
9907
Motor Frequency
See motor nameplate
(50 Hz, 60 Hz)
1103
Command Source Mode
0
1300
Analog Input 1 Signal Format
U 0-10
1301
Analog Input 1 Offset
23.5
1302
Analog Input 1 Scaling
1850
2007
Min Frequency Limit
0
2008
Max Frequency Limit
See motor nameplate
(50 Hz, 60 Hz)
2102
Stop Mode
0
2202
Accel Time
30.0
2203
Decel Time
30.0
2601
Energy Optimizer
0
GROUP NAVIGATION
PARAMETER STRUCTURE
LD29434
FIGURE 37 -
DRIVE DISPLAY
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...