SECTION 4 – INSTALLATION
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
4
Generally, the thermal dispersion flow switch is
shipped with the unit as a loose part.
To mount the IFM thermal dispersion switch, use the
following guidelines:
• Use a pipe coupling to mount the thermal disper-
sion flow switch. The length of the pipe coupling
must be suitable to ensure that the insertion depth
of the sensor is at least 12 mm.
•
Mount the thermal dispersion flow switch in hori
-
zontal pipes from the side. If it has to be mounted
in vertical pipes, mount the switch in the rising
pipes.
•
Mount the thermal dispersion flow switch on the
top of the horizontal pipes only if the pipe is fully
filled with liquid. Mount the thermal dispersion
flow switch on the bottom of the horizontal pipes
only if the pipe is free from buildup.
• Ensure that the sensor tip does not contact the pipe
wall. Do not mount it in a downpipe, in which the
liquid flows downwards.
• Avoid turbulence of the liquid resulting from
bends, valves, reducers, and other pipe fittings.
Ensure that the distance from the potential turbu-
lence upstream or downstream of the sensor loca-
tion is at least 5 times of the pipe diameter.
•
Connect the control monitor with the flow sensor
directly. No extension cable between them is al-
lowed.
Содержание YLAA0041
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 ICOM6 ISSUE DATE 12 18 2020 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 32: ...JOHNSON CONTROLS 32 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 110: ...JOHNSON CONTROLS 110 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 122: ...JOHNSON CONTROLS 122 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 150 72 ICOM6 ISSUE DATE 08 03 2022 THIS PAGE IS INTENTIONALLY LEFT BLANK...