UNIT LOCATION
The YLAA chillers are designed for outdoor installation. When selecting a site for installa-
tion, be guided by the following conditions:
A. For outdoor locations of the unit, select a place having an adequate supply of fresh air
for the condenser.
B. Avoid locations beneath windows or between structures where normal operating
sounds may be objectionable.
C. Installation sites may be either on a roof, or at ground level. (See FOUNDATION.)
D. The condenser fans are the propeller-type, and are not recommended for use with duct
work in the condenser air stream.
E. When it is desirable to surround the unit(s), it is recommended that the screening be
able to pass the required chiller CFM without exceeding 0.1" of water external static
pressure.
F. Protection against corrosive environments is available by supplying the units with ep-
oxy coating on the condenser coils. The epoxy coils should be offered with any units
being installed at the seashore or where salt spray may hit the unit.
In installations where winter operation is intended and snow accumulations are expected,
additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in Dimensions. When the available space is
less, the unit(s) must be equipped with the discharge pressure transducer option to permit
high pressure unloading in the event that air recirculation were to occur.
FOUNDATION
The unit should be mounted on a flat and level foundation, ground or roof, capable of sup-
porting the entire operating weight of the equipment. Operating weights are given in the
Physical Data and Nominal Ratings on page 22
tables.
Roof Locations
– Choose a spot with adequate structural strength to safely support the
entire weight of the unit and service personnel. Care must be taken not to damage the roof
during installation. If the roof is “bonded”, consult the building contractor or architect for
special installation requirements. Roof installations should incorporate the use of spring-
type isolators to minimize the transmission of vibration into the building structure.
Ground Level Installations
– It is important that the units be installed on a substantial
base that will not settle, causing strain on the liquid lines and resulting in possible leaks.
A one-piece concrete slab with footers extending below the frost line is highly recom-
mended. Additionally, the slab should not be tied to the main building foundation as noises
will telegraph.
Mounting holes (5/8" diameter) are provided in the steel channel for bolting the unit to its
foundation. See
Unit Dimensions on page 26
.
Application Data
Содержание YLAA
Страница 4: ...JOHNSON CONTROLS FORM 150 72 EG6 516 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 35: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 35 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 48: ...JOHNSON CONTROLS FORM 150 72 EG6 516 48 Wiring Diagram ...
Страница 49: ...FORM 150 72 EG6 516 JOHNSON CONTROLS 49 LD18444 Wiring Diagram Cont d ...