T2 accessory for units with infra-red remote control and/or MB electronic board
T2
sensor to be placed on the water supply pipe upstream 3 way valves (not to be used with 2 way valve). The
T2
sensor must
be used as described below:
•
Change-Over for the automatic switch of the operating mode. If water temperature is lower than 20°C, cooling mode is set; on the
other hand, if water temperature exceeds 30°C, heating mode is set.
•
It can be used on units with electric heater and hot water supply. The
T2
priority probe activates the electric heater or water valve,
depending on the water temperature detected. If water temperature exceeds 34°C, the water valve ON-OFF control is activated; on
the other hand, if water temperature is lower than 30°C, the electric heater is activated.
ID
Code
T2
9025310
A group of
YHVP
units with
MB
electronic board can be connected via a serial link and can consequently be managed at the
same time by just one
JTM-B
wall control or
RT03
infra-red remote control. Using the special jumper present on the MB board,
one unit must be configured as the master, and all the others as slaves. The remote control must be pointed at the receiver on
the master unit. To avoid problems, it is recommended to install and connect the receiver only on the master unit.
With JTM-B wall control
With RT03 infra-red remote control
Controls and units
MB version
One control for each unit
One control for more units
(20 units max.)
(M
AXIMUM
TOTAL
LENGTH
OF
THE
CONNECTION
CABLE
= 800
M
)
One control for each unit
(M
AXIMUM
LENGTH
OF
THE
CONNECTION
CABLE
= 20
M
)
One control for more units
(20 units max.)
(M
AXIMUM
TOTAL
LENGTH
OF
THE
CONNECTION
CABLE
= 800
M
)
Max
20 m
Max
20 m
Belden
9841
Cable
Belden
9841
Cable