6
YHVP
YHVP
Serie
6
EUROVENT certifications
(E) = Eurovent certified performance.
MIN-MED-MAX
= Standard connected speeds.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m
3
room
and a reverberation time of 0.5 sec.
Technical features
MODEL
YHVP 1
YHVP 2
Speed
1 (E)
2 (E)
3
4 (E)
5
6
1 (E)
2
3 (E)
4
5 (E)
6
MIN
MED
MAX
MIN
MED
MAX
Air flow
m
3
/h
205
270
340
375
470
500
250
305
365
400
480
545
Cooling total emission (E)
kW
1,24
1,50
1,76
1,87
2,15
2,23
1,43
1,63
1,84
1,95
2,18
2,35
Cooling sensible emission (E)
kW
0,92
1,14
1,36
1,46
1,72
1,80
1,07
1,25
1,43
1,53
1,75
1,92
Heating (E)
kW
1,60
2,00
2,39
2,58
3,04
3,17
1,88
2,20
2,39
2,70
3,09
3,38
ΔP Cooling (E)
kPa
4,8
6,8
9,0
10,1
13,0
13,9
6,2
7,9
9,8
10,9
13,3
15,2
ΔP Heating (E)
kPa
3,7
5,5
7,2
8,3
10,6
10,8
4,8
6,4
7,2
8,5
10,9
12,5
Fan (E)
W
12
14
17
18
24
30
12
14
18
20
24
32
Sound power (E)
Lw dB(A)
35
41
46
48
52
53
39
43
47
49
53
55
Sound pressure (*)
Lp
dB(A)
26
32
37
39
43
44
30
34
38
40
44
46
MODEL
YHVP 3
YHVP 4
Speed
1 (E)
2 (E)
3
4 (E)
5
6
1
2 (E)
3
4 (E)
5
6 (E)
MIN
MED
MAX
MIN
MED
MAX
Air flow
m
3
/h
280
375
480
545
730
780
300
440
500
610
675
790
Cooling total emission (E)
kW
1,89
2,32
2,78
3,03
3,63
3,78
1,99
2,62
2,86
3,26
3,46
3,81
Cooling sensible emission (E)
kW
1,35
1,69
2,06
2,27
2,81
2,95
1,43
1,93
2,12
2,47
2,66
2,98
Heating (E)
kW
2,26
2,84
3,49
3,86
4,79
5,03
2,40
3,26
3,61
4,20
4,53
5,07
ΔP Cooling (E)
kPa
11,2
16,2
22,5
26,2
36,4
39,1
12,3
20,2
23,6
29,9
33,4
39,7
ΔP Heating (E)
kPa
8,7
12,6
17,7
21,2
29,3
31,9
9,7
15,9
19,1
23,7
27,2
31,5
Fan (E)
W
16
21
26
29
38
46
17
23
27
32
35
48
Sound power (E)
Lw dB(A)
35
40
45
48
55
57
36
43
46
51
54
57
Sound pressure (*)
Lp
dB(A)
26
31
36
39
46
48
27
34
37
42
45
48
www.eurovent-certification.com
www.certiflash.com
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water flow rate as for the cooling conditions
2-pipe units
The following standard rating conditions are used: