20
20
YHVP-ECM
YHVP-ECM
Serie
20
EUROVENT certifications
(E) = Eurovent certified performance.
MIN-MED-MAX
= Standard connected speeds.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m
3
room
and a reverberation time of 0.5 sec.
Technical features
MODEL
YHVP-ECM 1
YHVP-ECM 2
Inverter power
1 (E)
3
5 (E)
7,5
10 (E)
1 (E)
3
5 (E)
7,5
10 (E)
MIN
MED
MAX
MIN
MED
MAX
Air flow
m
3
/h
190
240
290
355
415
260
315
375
440
510
Cooling total emission (E)
kW
1,17
1,39
1,58
1,81
2,00
1,47
1,67
1,87
2,07
2,26
Cooling sensible emission (E)
kW
0,86
1,04
1,20
1,40
1,57
1,10
1,28
1,46
1,64
1,83
Heating (E)
kW
1,50
1,82
2,12
2,48
2,78
1,94
2,25
2,58
2,90
3,23
ΔP Cooling (E)
kPa
5,0
6,3
7,7
9,5
11,2
6,9
8,4
10,1
11,8
13,7
ΔP Heating (E)
kPa
4,2
5,4
6,5
8,2
9,3
5,6
6,9
8,5
9,7
11,6
Fan (E)
W
6
7
9
11
15
7
9
12
16
21
Sound power (E)
Lw dB(A)
35
39
46
48
52
40
44
47
51
55
Sound pressure (*)
Lp
dB(A)
26
30
37
39
43
31
35
38
42
46
MODEL
YHVP-ECM 3
YHVP-ECM 4
Inverter power
1 (E)
3
5 (E)
7,5
10 (E)
1 (E)
3
5 (E)
7,5
10 (E)
MIN
MED
MAX
MIN
MED
MAX
Air flow
m
3
/h
270
345
420
520
620
375
465
550
665
770
Cooling total emission (E)
kW
1,83
2,20
2,53
2,93
3,29
2,34
2,72
3,05
3,43
3,75
Cooling sensible emission (E)
kW
1,31
1,60
1,86
2,19
2,50
1,70
2,01
2,29
2,63
2,92
Heating (E)
kW
2,20
2,69
3,15
3,72
4,25
2,87
3,41
3,88
4,48
4,99
ΔP Cooling (E)
kPa
10,7
14,8
19,0
24,8
30,4
16,5
21,6
26,6
32,9
38,7
ΔP Heating (E)
kPa
8,5
11,7
15,1
19,9
24,2
12,6
17,2
21,2
26,6
31,4
Fan (E)
W
6
8
11
15
20
9
12
16
22
30
Sound power (E)
Lw dB(A)
37
42
45
49
53
43
46
49
53
57
Sound pressure (*)
Lp
dB(A)
28
33
36
40
44
34
37
40
44
48
www.eurovent-certification.com
www.certiflash.com
COOLING (summer operation)
Entering air temperature: + 27°C d.b. / + 19°C w.b.
Water temperature: + 7°C E.W.T. / + 12°C L.W.T.
HEATING (winter operation)
Entering air temperature: + 20°C
Water temperature: + 50°C E.W.T.
Water flow rate as for the cooling conditions
2-pipe units
The following standard rating conditions are used:
Содержание YHVP