28
YHVP/YHVP-ECM
YHVP/YHVP-ECM
Serie
Controls and units
T version
Stand alone units: the infra-red remote control can control one unit only
RT03
I
NFRA
-
RED
REMOTE
CONTROL
The electronic board, mounted as per standard on the
YHVP-T
and
YHVP-ECM-T
, is set to carry out different functions and
adjustment modes, in order to meet the installation requirements. These modes are selected by setting the configuration dip
switches on the board.
• Fan ON/OFF thermostatic control.
• Valve ON/OFF thermostatic control and continuous
ventilation.
• Valve and simultaneous ventilation ON/OFF thermostatic
control.
• Fan operation control depending on the coil temperature
(cut-out T3 probe fitted), which can be activated only in
heating mode or heating and cooling mode.
• Automatic switch of the operating mode by means of T2
water probe (optional).
• Seasonal switch by means of remote contact.
• ON/OFF of the fan coil by means of the remote contact (window or clock contact).
• Electric heater control
By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°C and
started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside the coil exceeds 22°C
and starts when it drops below 18°C.
The infra-red remote control allows setting by a remote position the fan coil operation parameters.
The
RT03
infra-red remote control features the following functions:
• Switch the appliance ON and OFF.
• Temperature set.
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating).
• Time setting.
• 24 hours ON/OFF program.
Содержание YHVP
Страница 38: ......
Страница 40: ...YHVP 04 16 CODE 99A4250142 E 04 16 ...