FORM 150.75-NM2
85
YORK INTERNATIONAL
When the Low Ambient Option is installed, the following
physical changes are made to the standard chiller:
1. Discharge pressure transducers and wiring are added
to both modules.
2. Reversing contactors 9M, 10M, 15M and 16M with
supporting wiring are added to both the Master and
Slave Control Panels.
3. A second Relay Output Board and wiring is installed
in both Control Panels.
Programming
The control panel may be programmed for AMBIENT
& DISCH PR FAN CONTROL (Ambient & discharge
pressure fan control) or by DISCHARGE PRESSURE
FAN CONTROL (fan control by discharge pressure
only). This is selected by placing SW8 on both the Mas-
ter and Slave Microprocessor Boards to the appropri-
ate position. See page 40.
SW2 on each microprocessor board must also be pro-
grammed for LOW AMBIENT CONTROL to allow
operation at temperatures below 25°F. To accomplish
this, place SW2 in the CLOSED position. See page 39.
After the switch is properly positioned, the OUTSIDE
AIR TMP LOW CUT-OUT in the PROGRAM mode can
then be programmed between 0° - 25°F. See page 46.
NOTE: For operation below 0°F, program the cut-out
for 0°F. This will cause the microprocessor to
ignore the low ambient cut-out regardless of
temperature.
Operation of the fans will be discussed in both Ambi-
ent and Pressure Control as well as Pressure Only
control in the following text.
Ambient and Pressure Fan Control
0°F - 25°F
Fan operation on each system below 25°F is controlled
only by the discharge pressure of the respective sys-
tem. Each system will operate 4 steps of fan control as
follows:
1. Until discharge pressure reaches 320 PSIG, the fans
will be completely off.
2. The second stage of fan control will energize fans 1
& 3 (SYS 1, 9M and 10M), fans 5 & 7 (SYS 2, 15M
&16M), fans 9 & 11 (SYS 3, 9M and 10M) or fans 13
& 15 (SYS 4, 15M & 16M) in the reverse direction
when the discharge pressure exceeds 320 PSIG.
Once the reversing contactors are energized, they
will stay on until the discharge pressure of the sys-
tem falls below 120 PSIG, the ambient temperature
exceeds 35°F, or discharge pressure of the system
rises above 340 PSIG.
NOTE: The corresponding compressor must be on
for a minimum of 4 sec. before the reversing
fans are permitted to start.
3. The third stage of fan control will energize fans 2 & 4
(SYS 1, 6M & 8M), fans 6 & 8 (SYS 2, 12M & 14M),
fans 10 & 12 (SYS 3, 6M and 8M) or fans 14 & 16
(SYS 4, 12M & 14M) as well as turn off the reversing
fans on the respective system whenever discharge
pressure exceeds 340 PSIG. These fans will stay on
until discharge pressure drops below 120 PSIG.
NOTE: The corresponding compressor must be on
for 4 sec. before these fans are permitted to
start.
4. The fourth stage of fan control will energize fans 1 &
3 (SYS 1, 5M & 7M) or fans 5 & 7 (SYS 2, 11M &
13M), fans 9 & 11 (SYS 3, 5M & 7M) and fans 13 &
15 (SYS 4, 11M & 13M) and will operate the corre-
sponding fans in the forward direction whenever dis-
charge pressure exceeds 360 PSIG. These fans will
stay on until discharge pressure drops below 140
PSIG.
NOTE: The corresponding compressor must be on for
4 sec. before these fans are permitted to start.
Ambient and Pressure Fan Control
25° - 45°F
Fan control between 25°and 35°F is controlled by dis-
charge pressure. If the reversing fans are on, the revers-
ing fan will continue to operate until the temperature
reaches 35°F or discharge pressure reaches 340 PSIG.
At 35°F or 340 PSIG, fans 2 & 4 (SYS 1, 6M & 8M), fans
6 & 8 (SYS 2, 12M & 14M), or fans 10 & 12 (SYS 3, 6M
& 8M) or fans 14 & 16 (SYS 4, 12M & 14M) will energize.
Between 25°F and 45°F if the reversing fan is not oper-
ating, after 4 seconds of compressor operation, fans 2 &
4 (SYS 1), fans 6 & 8 (SYS 2), fans 10 & 12 (SYS 3) or
fans 14 & 16 (SYS 4) will energize. This is identical to
standard fan control by temperature (Page 82). No pres-
sure override exists. If temperature drops below 25°F,
these fans will remain on until cycled off by pressure.
Ambient and Pressure Fan Control
45°F and Higher
Fan control above 45°F is strictly controlled by tempera-
ture with no pressure override.
After 4 seconds of operation, fans 2 & 4 (SYS 1, 6M &
8M), fans 6 & 8 (SYS 2, 12M & 14M), fans 10 & 12
(SYS 3, 6M & 8M) or fans 14 & 16 (SYS 4, 12M & 14M)
will energize turning the fans in the forward direction.
Содержание YDAJ87KU6
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...