![York YDAJ87KU6 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/york/ydaj87ku6/ydaj87ku6_manual_4193144050.webp)
YORK INTERNATIONAL
50
Once the desired information is keyed in, it may be stored
in memory by pressing the ENTER key. After the EN-
TER key is pressed, the cursor will move under the T of
TODAY.
The micro will accept any valid time or date. If an out of
range value is entered, the micro will display the follow-
ing message for 3 seconds before it reverts back to the
SET TIME display message to let the user know that
another try at reprogramming is necessary.
PROGRAMMING THE DAILY START/STOP AND
HOLIDAY SCHEDULE
Set Schedule/Holiday
Messages showing the start/stop schedule of each day
of the week as well as the holiday start/stop schedule
can be displayed after the SET SCHEDULE/HOLIDAY
key is pressed. The display can be scrolled through day-
by-day simply by repetitively pressing the ENTER or
ADVANCE DAY key. A typical daily schedule display is
shown below:
To reprogram any of the daily schedules, key in the new
START time. To change the AM/PM associated with the
START time, press the AM/PM key. This will change
the AM/PM message to the opposite time period. The
AM/PM key can only be pressed once. If an error is
made, press CANCEL and begin reprogramming again.
After the START time and the associated AM/PM have
been programmed, the cursor will move to the STOP
time. Key in the STOP TIME and press the AM/PM
key if AM/PM requires changing.
When the ENTER key is pressed, the new START/
STOP time is entered and the display will scroll to the
next day. If an unacceptable time is entered, the follow-
ing message will be displayed.
For ease of programming, any values ENTERED for
MONDAY will
automatically
be put in for the other days
of the week. Be aware of this anytime the MONDAY
SCHEDULE is changed, since it changes times previ-
ously programmed into other days. For scrolling through
the days to view times programmed use the ADVANCE
DAY KEY, not the ENTER KEY. This will assure that
after viewing MONDAY, that the ENTER KEY is not
pressed changing times programmed for the rest of the
week.
If the chiller is not cycled by the DAILY SCHEDULE, but
is required to run whenever the system switches are
on, all 00.00s should be programmed into the daily
schedule. This can be done manually for each day or
by pressing CANCEL and ENTER when the MONDAY
START/STOP schedule appears.
NOTE: This will have no effect on the holiday schedule.
Continue to program each day as needed. After MON
through SUN has been entered, the HOLIDAY message
will be displayed.
The Holiday (HOL) START/STOP allows the user to des-
ignate a specific day(s) for special requirements. This
is provided so that day(s) needing special start/stop re-
quirements can be programmed without disturbing the
normal working schedule.
The start/stop times for the Holiday schedule are pro-
grammed just as for any other day.
NOTE: Only one start/stop time can be programmed
which will apply to each of the HOLIDAY days
selected.
After the ENTER key is pressed, a new message will
be displayed to designate which days of the week are
to be holidays.
In the above sample display, an * designates Tuesday
as a holiday.
When the display appears, the cursor will first stop be-
hind Sunday. To designate a day as a holiday, press the
* key. If a day is not to be a holiday, press the 0 key.
Whenever the * or the 0 keys are pressed, the cur-
sor will advance to the next day. After all the holiday
days are programmed, press ENTER to store the new
data into memory. The display will then advance to the
beginning of the Daily Schedule (MON).
The Holiday Schedule is only executed once by the
micro before it is erased from memory. This is done
O U T
O F
R A N G E
T R Y
A G A I N !
M O N
S T A R T
=
0 6 : 0 0 A M
S T O P
=
0 5 : 3 0 P M
O U T
O F
R A N G E
T R Y
A G A I N !
H O L
S T A R T
=
0 8 : 0 0 A M
S T O P
=
1 2 : 0 0 P M
S
M
T *
W
T
F
S
H O L I D A Y
N O T E D
B Y
*
SET SCHEDULE
/ HOLIDAY
Содержание YDAJ87KU6
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...