![York YDAJ87KU6 Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/york/ydaj87ku6/ydaj87ku6_manual_4193144066.webp)
YORK INTERNATIONAL
66
The Run Time for SYS 4 since the last start is displayed.
History
The HISTORY key also allows the user to scroll through
the SAFETY SHUTDOWN buffers to display informa-
tion relating to the last 3 Safety Shutdowns which oc-
curred. Information contained in the SAFETY SHUT-
DOWN Buffers is very important when attempting to
troubleshoot a system problem. This data reflects sys-
tem conditions at the
instant
the fault occurred.
Information is stored in the SAFETY SHUTDOWN Buff-
ers on every fault regardless of whether the fault caused
a Lockout to occur. The information is also not affected
by power failures (long term internal memory battery
back-up is built into the circuit board) or manual reset-
ting of a fault lock-out.
When the HISTORY key is passed, the following mes-
sage will appear.
The operator must then select which SAFETY SHUT-
DOWN Buffer is desired. When deciding this, keep in
mind that Buffer No. 1 is always the most recent fault.
As new fault information is stored, it is always placed in
Buffer No. 1, No. 1 is loaded to No. 2, No. 2 is loaded to
No. 3, and information previously in No. 3 is discarded.
To select a buffer, simply press the 1, 2, or 3 EN-
TRY key and press ENTER. Repetitively pressing the
ENTER key will allow the operator to scroll through the
information available in the SAFETY SHUTDOWN
Buffer.
In the information that follows, a sample message along
with an explanation is provided for all available mes-
sages.
This message informs the operator of the time and date
of the fault.
This message informs the operator of the nature of the
fault which occurred if it is on the MASTER Module.
OFF: SYS 3 Liquid Line Solenoid De-energized
(Closed).
ON: SYS 3 Liquid Line Solenoid Energized (Open).
This message informs the operator of the number of
stages of loading which are active on SYS 3.
This message informs the operator of the number of
forward running fans which are active on SYS 3.
This message informs the operator whether the revers-
ing fan is active on SYS 3.
The Run Time for SYS 3 since the last start is displayed.
OFF: SYS 4 Liquid Line Solenoid De-energized
(Closed).
ON: SYS 4 Liquid Line Solenoid Energized (Open).
This message informs the operator of the number of
stages of loading which are active on SYS 4.
This message informs the operator of the number of
forward running fans which are active on SYS 4.
This message informs the operator whether the revers-
ing fan is active on SYS 4.
S Y S
3
L I Q U I D
L I N E
S O L E N O I D
S T A T U S
O F F
S Y S
3
S T A G E S
O F
L O A D I N G
2
S Y S
3
F O R W A R D
F A N S
S T A T U S
S Y S
3
R E V E R S E
F A N S
S T A T U S
O F F
S Y S
3
R U N
T I M E
2 0 0
S E C S
D I S P L A Y
S A F E T Y
S H U T -
D O W N
N O . 1
( 1
T O
3 )
S H U T D O W N
O C C U R R E D
3 : 2 4 P M
3 / 1 2 / 9 5
S Y S # 1
L O W
O I L
P R E S S
S Y S # 2
N O
F A U L T S
S Y S
4
L I Q U I D
L I N E
S O L E N O I D
S T A T U S
O N
S Y S
4
S T A G E S
O F
L O A D I N G
1
S Y S
4
F O R W A R D
F A N S
S T A T U S
O F F
S Y S
4
R E V E R S E
F A N S
S T A T U S
O F F
S Y S
4
R U N
T I M E
0
S E C S
Содержание YDAJ87KU6
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...