GENERAL
After Switch #4 of Dip Switch S1 on both Micro Boards
is properly configured to select Leaving Control, the
chilled liquid setpoints can then be programmed into
the Control Panel. Switch #4 of S1 must be properly
programmed or an incorrect display message will ap-
pear when the CHILLED LIQUID TEMP/RANGE key is
pressed. See CHILLED LIQUID CONTROL Page 51
if needed.
If remote temperature setpoint is being utilized, the RE-
MOTE RESET TEMP RANGE must be programmed.
Programming the REMOTE RESET TEMP RANGE is
discussed later in this manual on page 75.
PROGRAMMING LEAVING WATER CONTROL
Chilled Liquid
Temp/Range
When the CHILLED LIQUID TEMP/RANGE key is
pressed, the following message will be displayed for 3
seconds indicating Dip Switch S1, Switch #4 on both
Microprocessor Boards is programmed properly:
26572A
SETPOINTS KEYS
PROGRAMMING CHILLED LIQUID SETPOINTS &
REMOTE RESET TEMP RANGE
L W T =
4 4 . 0
F
C R =
4 4 . 0
T O
4 6 . 0
F
CHILLED LIQUID
TEMP / RANGE
SETPOINTS
KEYS
L E A V I N G
W A T E R
T E M P
C O N T R O L
If this message is incorrect, see the CHILLED LIQUID
CONTROL Section (Page 51) for instructions to repro-
gram the Microprocessor Dip Switch S1, Switch #4.
The display will then scroll to a second message & hold:
This message will then display the Low-Limit Water
Temperature (LWT) and the Control Range (CR). In the
sample above, the LWT is 44.0°F and the CR is 44° -
46°F.
The Control Range (CR) is the variation is leaving wa-
ter temperature which is acceptable in the system ap-
plication. As long as leaving water temperature stays
between the low limit and midpoint of the Control Range
(CR), the Microprocessor will consider the temperature
acceptable and will not initiate any loading / unloading
reaction unless Rate Control requires. The Low-Limit
Water Temperature (LWT) is the minimum acceptable
leaving water temperature in the Control Range (CR),
not the actual user desired leaving water temperature.
The desired leaving water temperature is known as the
Target temperature which is the temperature the mi-
cro will attempt to control too. The Target temperature
is not programmable, but it is always the midpoint of
the Control Range (CR). Example: A control range of
44° - 46°F will have a Target Temp of 45°F, which
Содержание YDAJ87KU6
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...