YORK INTERNATIONAL
54
In the lower half of the Control Range between the Low-
Limit Water Setpoint (LWT) and the Target Tempera-
ture (Desired Leaving Water Temperature), Rate Con-
trol software will cause unloading if temperature drops
faster than 1X the Rate Sensitivity. Otherwise, no other
loading or unloading will result in this temperature range.
In the upper half of the Control Range between the TAR-
GET and the High Limit of the Control Range and in
the Rate Control Range, loading will take place in 150
sec. intervals until temperature drops below the TAR-
GET temperature. The Rate Control software may pre-
vent loading or possibly initiate unloading if tempera-
ture drops faster than 2X the programmed Rate Sensi-
tivity.
Above the RATE CONTROL TEMP RANGE, the micro
will attempt to load the chiller as fast as it can (30 sec-
onds per stage) unless the chiller has not run for 3 min-
utes during which loading will occur at 1 min. intervals.
This allows the chiller to gain control of the water tem-
perature as quickly as possible while still avoiding over-
shoot and limiting pulldown demand as temperature
drops and rate control is implemented.
Since LWT Control does not have the water loop for
buffering after a load/unload response and utilizes a
narrow control (loading/unloading) range, compressor/
loader cycling can be a problem. This makes the selec-
tion of RATE CONTROL TEMP and RATE SENSITIV-
ITY values very critical.
Before programming the RATE CONTROL TEMP, the
user should first determine if typically the fastest allow-
able pulldowns are required or weather pulldown de-
mand limiting is desired. Programmable values from
0.1-20°F are possible.
For normal pulldowns, and quick response, a RATE
CONTROL TEMP of 0.1°F is appropriate unless over-
shoot is noted.
For demand limiting, energy efficiency, elimination of
overshoot, and minimum cycling, RATE CONTROL
TEMPS of 10°-20°F are advisable. This will cause the
controls to react to water temperature rate of change
well before the water temperature drops into the CON-
TROL RANGE. This may be required for small water
loops. However, if problems arise where the chiller does
not load and pull temperature down, select 0.1°F.
To program the RATE CONTROL TEMP, first press the
PROGRAM key. Repetitively press the ENTER key un-
til the display below appears.
PROGRAMMING
LEAVING WATER RATE CONTROL
Programmable RATE CONTROL is designed to limit
compressor/loader cycling thus saving energy and re-
ducing wear on mechanical components. It also reduces
the possibility of overshoot. RATE CONTROL will al-
low the micro to react to fast changes in water tem-
perature beyond normal responses dictated by leaving
water temperatures, the 150 sec. loading timer, and the
20 sec. unloading temperature when temperatures are
in the Rate Control Range or the Control Range.
RATE CONTROL requires programming the tempera-
ture range (RATE CONTROL TEMP) above the CON-
TROL RANGE (CR) where rate control is desired. Ad-
ditionally, the actual rate of change (RATE SENSITIV-
ITY) of water temperature which the micro uses as a
control reference must also be programmed.
Refer to Fig. 26 as you read the following text. A typical
low limit water temperature of 44°F is used with a 44° -
46°F CONTROL RANGE (CR). A RATE CONTROL
TEMP of 10°F, which is typical (10° above upper limit
of the Control Range), is shown.
The RATE CONTROL TEMP establishes a tempera-
ture range (0.1 - 20°F) above the Upper Limit of CON-
TROL RANGE where the micro will limit loading if the
rate of change of water temperature exceeds the RATE
SENSITIVITY. In the above example a RATE CON-
TROL TEMP of 10°F is used. In the Rate Control Range,
the micro will prevent loading or may cause unloading
if the temperature drop exceeds 2X the Rate Sensitiv-
ity regardless of whether the 150 sec. loading timer and
the deviation from setpoint is calling for loading.
At temperatures below the CONTROL RANGE, unload-
ing will occur to bring temperatures back to within the
CONTROL RANGE. The unloading timer will cause un-
loading at 20 sec. intervals until temperatures fall back
into the CONTROL RANGE.
R A T E
C O N T R O L
T E M P
=
1 0 . 0 F
ý
ý
ý
ý
56°
46°
45°
44°
ABOVE THE RATE CONTROL
TEMP RANGE
UPPER LIMIT OF
CR PLUS RATE
CONTROL TEMP
RATE CONTROL TEMP RANGE
(RATE CONTROL TEMP = 10°F)
UPPER LIMIT OF
CONTROL RANGE
(CR)
CONTROL RANGE (CR)
TARGET
(CR = 45 - 46°F)
LOW LIMIT
OF CONTROL
BELOW THE
RANGE (LWT)
CONTROL RANGE
FIG. 26
LEAVING WATER TEMPERATURE CONTROL
Содержание YDAJ87KU6
Страница 4: ...YORK INTERNATIONAL 4 FIG 1 UNIT COMPONENTS Typical on each of the two modules 00023TG 00024TG...
Страница 5: ...FORM 150 75 NM2 5 YORK INTERNATIONAL FIG 1 UNIT COMPONENTS Cont d LD01910 00025TG...
Страница 24: ...YORK INTERNATIONAL 24 MASTER MODULE WIRING DIAGRAM LD01933 FIG 17 MASTER MODULE CONNECTION DIAGRAM...
Страница 30: ...YORK INTERNATIONAL 30 SLAVE MODULE WIRING DIAGRAM FIG 20 SLAVE MODULE CONNECTION DIAGRAM LD01941...
Страница 99: ...FORM 150 75 NM2 99 YORK INTERNATIONAL...