JOHNSON CONTROLS
160
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
SECTION 10 - MAINTENANCE
TABLE 35 – REAL TIME ERROR NUMBERS
ERROR NUMBER
(##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
TABLE 34 – VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
PROTOCOL
BACNET MS/TP
MODBUS RTU
5
YORKTALK 2
DE MODIFIER ADDRESS
0 to 41943
(3)
1
-1
DE MODIFIER OFFSET
0 to 99
(4)
0
N/A
P1 PROTOCOL
BACNET
N/A
N/A
P1 MANUAL MAC ADDRESS
0-127
(1)
N/A
N/A
P1 BAUD RATE
9600 to 76800 or Auto Selectable
(1)
N/A
N/A
P1 PARITY
NONE
N/A
N/A
P1 STOP BITS
1
N/A
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127
(1)
N/A
P2 BAUD RATE
N/A
19,200
(2)
N/A
P2 PARITY
N/A
NONE
(2)
N/A
P2 STOP BITS
N/A
1
N/A
P2 HW SELECT BIT
N/A
RS-485 or RS-232
(1)
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
P1 HW SELECT BIT
N/A
N/A
N/A
CHILLER ID
N/A
N/A
0
1
As required by network
2
Or other as required by network
3
Number is multiplied by 100, set as required by network
4
Number is added to DE MODIFIER ADDRESS, set as required by network
5
Unit operating software version C.MMC.13.03 or later required for Modbus protocol
The table below shows set-up requirements for each communication protocol.
The table below shows the real time error numbers that
may be encountered during communication setup and
a description of each.
REBOOT REQUIRED (CYCLE POWER)
AFTER SETTINGS ARE CHANGED.
Содержание YCAL Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 130: ...JOHNSON CONTROLS 130 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 144: ...JOHNSON CONTROLS 144 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 173: ...FORM 150 66 NM3 ISSUE DATE 09 25 2020 173 JOHNSON CONTROLS 10 NOTES...