Voltage Peak ( N-L1, N-L2, N-L3 )
Displays the 3-phase peak voltages as mea sured by the
Harmonic Filter (Neutral to Line).
RMS Voltage ( L1-L2, L2-L3, L3-L1 )
Displays the 3-phase RMS Voltages across each line.
Voltage Total Harmonic Distortion ( L1, L2, L3 )
Displays the 3-phase voltage Total Harmonic Dis tor tion
(THD) measurements.
RMS Filter Current ( L1, L2, L3 )
Displays the 3-phase Filter current values as measured
by the Harmonic Filter.
Supply Current Total Demand Distortion
( L1, L2, L3 )
Displays the 3-phase Current Total Demand Distortion
(TDD) measurements.
RMS Supply Current L1, L2, L3
Displays the 3-phase RMS Voltages across each line.
PROGRAMMABLE
Local Motor Current Limit
Access Level Required
: OP ER A TOR
Allows the user to specify the maximum al lowed mo-
tor current (as a percentage of FLA). When the motor
cur rent reaches this value, the pre-rotation vanes will
not be permitted to open further. If the motor current
rises above this value, the pre-rotation vanes will close
to reduce the current to this value.
Pulldown Demand Limit
Access Level Required
: OP ER A TOR
Allows the user to specify the current limit val ue (as a
percentage of FLA) to which the chiller will be limited
during the speci
Þ
ed pulldown limit time. This value will
override the Motor Current Limit value during this time
period. This function is used to provide energy sav ings
following chiller start-up.
Pulldown Demand Time
Access Level Required
: OP ER A TOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chill er
starts.
NAVIGATION
Home
Access Level Re quired
: VIEW
Causes an instant return to the Home Screen.
VSD
Access Level Required
: VIEW
Returns to the VSD Screen.
2
Содержание R123
Страница 2: ...YORK INTERNATIONAL 2 FORM 160 55 O1 604...
Страница 11: ...FORM 160 55 O1 604 11 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT...
Страница 35: ...FORM 160 55 O1 604 35 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 37: ...FORM 160 55 O1 604 37 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 63: ...FORM 160 55 O1 604 63 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 67: ...FORM 160 55 O1 604 67 YORK INTERNATIONAL 2 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT...
Страница 73: ...FORM 160 55 O1 604 73 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 111: ...FORM 160 55 O1 604 111 YORK INTERNATIONAL THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN FORMAT 2...
Страница 136: ...YORK INTERNATIONAL 136 FORM 160 55 O1 604 Operational Maintenance LD00470 FIG 61 ASSEMBLY OF DEHYDRATOR...
Страница 155: ...FORM 160 55 O1 604 155 YORK INTERNATIONAL NOTES...