124
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
Slide valve position is APPROXI-
MATE and should be used for refer-
ence only. Under actual conditions the
compressor may be fully loaded be-
tween step 60 - 75 and fully unloaded
between step 0 - 40.
Superheats are the difference between the respective satu-
rated temperature (converted from pressure) and the ac-
tual. Display Limits for the System Pressures and Tem-
peratures displays are as follows:
Minimum and maximum values may
change as software (EPROM) revi-
sions are made.
*Below 9.0°F (13°C), the Suction
Temp. display will disappear. This will
in turn cause the Superheat display to
disappear.
3.4
AMBIENT TEMP KEY
When the Ambient Temperature key is pressed, ambi-
ent air temperature, as measured surrounding the chiller,
is displayed.
Display Limits: Minimum
-4.6°F
(-20.3°C)
Maximum 137.9°F
(58.8°C)
3.3
SYSTEM # DATA KEYS
Pressing one of the System # Data keys a number of
times scrolls through displays of differential oil pres-
sure (OIL), suction pressure (SP) and discharge pres-
sure (DP), oil temperature, suction temperature (ST),
discharge temperature (DT), saturated suction tempera-
ture, suction superheat, saturated discharge tempera-
ture, discharge superheat and compressor slide valve
position.
Examples of these displays are as follows where # is
the appropriate system number:
The Cooler Inlet Temp. display will
only appear if the chiller is selected for
R-407C.
Temperatures and pressures are either measured directly
by transducers and temperature sensors, or computed
from these measurements as follows:
Saturated discharge and suction temperatures are com-
puted by converting measured pressure to temperature.
Slide Valve Position is computed based on the number
of loading steps that the micro has sent to the slide valve
solenoid in the form of a current signal. To the micro-
processor, STEP 0 = fully unloaded and STEP 75 =
fully loaded.
A M B I E N T
A I R
T E M P
=
7 1 . 9
° F
S #
S A T
D S C H = 1 3 0 . 0 ° F
D S C H
S H E A T
=
5 4 . 3 ° F
S Y S
#
S
V
S T E P
=
3
S Y S
#
C O O L E R
I N L E T
R E F R I G
T E M P =
2 8 . 2 ° F
S Y S
#
O I L =
1 7 6
P S I G
S P =
6 4
D P =
1 9 5
P S I G
S Y S
#
O I L
=
1 5 7 . 4 ° F
S T =
3 1 . 0
D T =
1 2 3 . 2 ° F
S #
S A T
S U C T
=
3 2 . 9 ° F
S U C T
S H E A T
=
1 5 . 0 ° F
MIN. LIMIT
MAX. LIMIT
Oil Pressure
0 PSIG
(0 Bar)
399 PSIG
(28 Bar)
Suction Pressure
0 PSIG
(0 Bar)
199 PSIG
(14 Bar)
Discharge Pressure
0 PSIG
(0 Bar)
399 PSIG
(28 Bar)
Suction Temp.
*9.0 °F
(-13°C)
84.2 °F
(29°C)
Discharge Temp.
40.3 °F
(5°C)
302.6 °F
(150°C)
Oil Temp.
40.3 °F
(5°C)
240.0 °F
(116°C)
Sat. Discharge Temp.
-41.0 °F
(-41°C)
140.5 °F
(60°C)
Sat. Suction Temp.
-41.0 °F
(-41°C)
101.3 °F
(39°C)
Slide Valve Position
0%
(0%)
100%
(100%)
Suction Superheat
*-81.5 °F (-63.1°C)
60.9 °F
(16°C)
Discharge Superheat
22.5 °F
(-5.3°C)
216.0 °F (102.2°C)
Micro Panel Contents
Содержание MILLENNIUM YCAS0230
Страница 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Страница 61: ...61 YORK INTERNATIONAL FORM 201 18 NM1 102 WIRING DIAGRAM WYE DELTA START FIG 21 CONT D LD03229 7 ...
Страница 67: ...67 YORK INTERNATIONAL FORM 201 18 NM1 102 LD03282 LD03283 LD03284 FIG 25 DETAIL A see pages 56 57 7 ...
Страница 69: ...69 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR TERMINAL BOX LD03233 FIG 29 COMPRESSOR TERMINAL BOXES 7 ...
Страница 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Страница 95: ...95 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR COMPONENTS CONT D FIG 43 COMPRESSOR COMPONENTS LD03670 7 ...
Страница 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...
Страница 167: ...167 YORK INTERNATIONAL FORM 201 18 NM1 102 ...