119
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
High Discharge Pressure Cutout:
The Discharge Pressure Safety prevents system pres-
sure from exceeding safe working limits. This safety is
a backup for the mechanical High Pressure Cutout in
each system. The Discharge Pressure Safety is program-
mable for a range of values below the system upper
limit (see Section 8.2 / Page 143, High Discharge Pres-
sure Cutout for more details).
High Discharge Temperature Cutout:
This safety protects the compressor rotors from dam-
age due to overheating, expansion, and breakdown of
the oil film seal between the rotors. It also protects
against excessive oil temperature in the discharge oil
separator.
For the first 4 seconds of operation discharge tempera-
ture is ignored. After 4 seconds of operation the com-
pressor will shut down if the discharge temperature ex-
ceeds 260°F (127°C).
High Oil Differential Pressure Cutout:
The High Oil Pressure Differential Safety protects the
compressors against loss of proper lubrication due to
oil return line blockage. The “differential oil pressure”
for this safety is computed by measuring discharge (oil
separator) pressure and subtracting oil pressure return-
ing to the compressor (Discharge - Oil = Oil PSID).
Under normal operation, the oil pressure differential
display will be less than 25 PSID (1.7 bar), typical 2 -
10 PSID (0.1 to 0.7 bar). If oil pressure at the compres-
sor drops due to filter blockage, the differential pres-
sure on the display will increase and when the maxi-
mum limit is reached the compressor will be shut down.
This safety is activated after 3 minutes of operation.
Oil pressure must be less than 65 PSID (4.4 bar) for R-
22 models as long as the compressor continues to run.
the customer are connected in series with the flow
switch(es). YCAS 2 System chillers have a single flow
switch wired to the control panel. If the flow switch
opens, all systems will shut down and a NO RUN PERM
(Permissive) message will be displayed. Closing of the
flow switch, when flow is present, will cause the mes-
sage to disappear and auto-restart to occur.
Never bypass a flow switch. This will
cause damage to the chiller and void
any warranties.
2.6
SYSTEM FAULT (SAFETY) STATUS
MESSAGES
A System Fault will shut the affected system down
whenever a preset safety threshold is exceeded for 3
seconds. Automatic restart will occur after the first 2
shutdowns when the anti-recycle timer times out and
temperature demand exists. After any combination of
3 Manual Reset Safeties in a 90 minute time period, the
affected system will shut down and lock out on the last
fault. When one or more systems are shut down on one
of these safeties, a message will appear on the Status
display informing the operator of the problem.
The High Motor Current Safety is a
unique safety which will lock out a sys-
tem after only a single fault.
To reset a locked out system, turn the System Switch
for the affected system to the OFF position, then back
to the ON position (see Section 1.11, Page 111, Fig. 48
for switch locations).
Before returning a locked out system
to service, a thorough investigation of
the cause of the fault should be made.
Failure to repair the cause of the fault
while manually allowing repetitive re-
starts may cause further expensive
damage to the system.
S Y S
#
H I G H
D S C H
P R E S
S Y S
#
H I G H
D S C H
P R E S
S Y S
#
H I G H
D S C H
T E M P
S Y S
#
H I G H
D S C H
T E M P
S Y S
#
H I G H
O I L
D I F F
S Y S
#
H I G H
O I L
D I F F
8
Содержание MILLENNIUM YCAS0230
Страница 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Страница 61: ...61 YORK INTERNATIONAL FORM 201 18 NM1 102 WIRING DIAGRAM WYE DELTA START FIG 21 CONT D LD03229 7 ...
Страница 67: ...67 YORK INTERNATIONAL FORM 201 18 NM1 102 LD03282 LD03283 LD03284 FIG 25 DETAIL A see pages 56 57 7 ...
Страница 69: ...69 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR TERMINAL BOX LD03233 FIG 29 COMPRESSOR TERMINAL BOXES 7 ...
Страница 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Страница 95: ...95 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR COMPONENTS CONT D FIG 43 COMPRESSOR COMPONENTS LD03670 7 ...
Страница 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...
Страница 167: ...167 YORK INTERNATIONAL FORM 201 18 NM1 102 ...