116
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
System Switches OFF:
This message indicates that the system switch on the
Microprocessor Board for the respective system is in
the OFF position. A system can only run if the system
switch is in the ON position. The switch for System 1
and System 2 should normally be in the ON position
for all models. See Section 1.11, Figure 48, page 111 for
the location of the system switches.
Anti-Recycle Timers:
The anti-recycle timer message shows the amount of
time remaining before a compressor can be called to
restart. These 300 - 600 sec. timers begin timing when
a compressor starts, although a minimum of two min-
utes must always elapse after a compressor shuts down,
before it may again restart. If a power failure occurs,
the anti-recycle timers will reset to 120 seconds after
power is restored. The purpose of the timer is to allow
for motor cooling to dissipate the heat generated by in-
rush current at start-up.
Anti-Coincidence Timers:
The anti-coincident timer guards against two or more
compressors starting simultaneously. This avoids ex-
cessive instantaneous starting currents. A minimum of
60 seconds between compressor starts is maintained
even if demand is present and the anti-recycle timers
are timed out. The display shows the time before the
respective compressor can start. This display will only
appear after the anti-recycle timers have timed out.
Run Permissive Contacts OPEN:
This display indicates that an external cycling contact
and/or the flow switch connected to terminals 13 & 14
in the Logic Section(s) of the control panel(s) is/are
open. Whenever the contact(s) is /are open, the No Run
Permissive message will be displayed and the indicated
system will not run.
System Loading Requirement:
This message indicates that chilled liquid temperature is
below the point where the microprocessor will bring the
lead system on and/or that the loading sequence has not
loaded the chiller far enough to bring the lag system on.
The lag system will display this message until the load-
ing sequence is ready for the lag system to start.
2.3
UNIT WARNINGS
Unit Warnings are often caused by conditions which
require operator intervention to start the unit or extreme
operating conditions. All setpoints and programmable
values should be checked, if a chiller shutdown oc-
curred, before restarting the chiller. Unit Warnings are
not logged into the HISTORY BUFFER.
Low Battery Warning
On power-up the microprocessor will check the RTC
(Real Time Clock) memory back-up battery to make
sure it is still operational. Provided the battery checks
out, operation will continue normally. If a check is made
and the battery has failed, the microprocessor will not
allow the chiller to run and the above Status message
will appear.
If a low battery condition exists, the
micro will restore programmed cut-
outs, setpoints, and schedules to their
default values.
Once a low battery condition is detected, the only way
to run the chiller is to use the Manual Override key –
see Section 7.4 page 142. This allows reprogramming
of setpoints, cutouts, and schedule.
The U13 RTC chip should be replaced as soon as pos-
sible with Part No. 031-00955-000. Otherwise, the
chiller will shutdown and lose all programmed points,
and require a MANUAL OVERRIDE restart, if a power
failure occurs.
S Y S
#
D S C H
L I M I T I N G
S Y S
#
D S C H
L I M I T I N G
S Y S
#
A R
T I M E R
0
S
S Y S
#
A R
T I M E R
1 2 0
S
S Y S
#
C O M P
R U N N I N G
S Y S
#
A C
T I M E R
2 2
S
! !
L O W
B A T T E R Y
! !
C H E C K
P R O G / S E T P / T I M E
S Y S
#
N O
R U N
P E R M
S Y S
#
N O
R U N
P E R M
S Y S
#
N O
C O O L
L O A D
S Y S
#
N O
C O O L
L O A D
Micro Panel Contents
Содержание MILLENNIUM YCAS0230
Страница 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Страница 61: ...61 YORK INTERNATIONAL FORM 201 18 NM1 102 WIRING DIAGRAM WYE DELTA START FIG 21 CONT D LD03229 7 ...
Страница 67: ...67 YORK INTERNATIONAL FORM 201 18 NM1 102 LD03282 LD03283 LD03284 FIG 25 DETAIL A see pages 56 57 7 ...
Страница 69: ...69 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR TERMINAL BOX LD03233 FIG 29 COMPRESSOR TERMINAL BOXES 7 ...
Страница 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Страница 95: ...95 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR COMPONENTS CONT D FIG 43 COMPRESSOR COMPONENTS LD03670 7 ...
Страница 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...
Страница 167: ...167 YORK INTERNATIONAL FORM 201 18 NM1 102 ...