100
YORK INTERNATIONAL
FORM 201.18-NM1 (102)
q
5. Program the required operating values into the
micro for cutouts, safeties, etc. and record them
in the chart below. See Page 143 for details.
If Default Values are desired for programming
convenience, press the PROGRAM key, 6140,
and ENTER. This loads default values. Record
these values in the chart below.
PROGRAMMED VALUES
Refrigerant Type = _________________________
Disch Press Cutout = ______________ PSIG (kPa)
Disch Press Unld = ________________ PSIG (kPa)
Suction Press Cutout = _____________ PSIG (kPa)
High Amb Cutout = ____________________ °F (°C)
Low Amb Cutout = ____________________ °F (°C)
Leaving Chilled Liquid Temp Cutout = ______ °F (°C)
High Motor Current Unload = ____________ % FLA
Anti-Recycle Time = ____________________ Secs
q
6. Program the Chilled Liquid Setpoint/Range and
record:
Setpoint = __________________ °F (°C)
Range = ________ to ________ °F (°C)
Keep in mind that the target temperature dis-
played by the micro should equal the desired
leaving water temperature.
q
7. Ensure that the CLK jumper J18 on the Micro-
processor Board is in the ON position (Top 2
pins).
q
8. Set the Time and Date.
q
9. Program the Daily Schedule start and stop times.
Panel Checks
(Power ON – Both System Switches “OFF”)
q
1. Apply 3-phase power and verify its value (See
Fig. 8 and 9 pages 31 and 32).
q
2. Apply 115VAC and verify its value on the ter-
minal block in the lower left of the Power Panel.
Make the measurement between terminals 5 and
2 (See Fig. 13, page 36). The voltage should be
/- 10%.
q
3. Ensure the heaters on each compressor are on.
Allow the compressor heaters to remain on a
minimum of 24 hours before start-up. This is
important to ensure that no refrigerant is in the
compressor oil at start-up!
q
4. Program the dip switches on the microproces-
sor board for the desired operating requirements.
See Fig. 54, page 126. OPEN = Left side of
switch pushed down. CLOSED = Right side of
switch pushed down.
Verify the selections by pressing the OPTIONS
Key on the control panel. Check them off.
Damage to the chiller could result if
switches are improperly programmed.
Dip switches 4 through 8 are spares
and have no function.
SWITCH
SWITCH “OPEN”
SWITCH “CLOSED”
SETTING
SETTING
1
Water Cooling
Brine Cooling
2
Standard Ambient
Low Ambient
Control
Control
3
Refrigerant R-407C
Refrigerant R-22
Technical Data
Содержание MILLENNIUM YCAS0230
Страница 45: ...45 YORK INTERNATIONAL FORM 201 18 NM1 102 This page intentionally left blank 7 ...
Страница 61: ...61 YORK INTERNATIONAL FORM 201 18 NM1 102 WIRING DIAGRAM WYE DELTA START FIG 21 CONT D LD03229 7 ...
Страница 67: ...67 YORK INTERNATIONAL FORM 201 18 NM1 102 LD03282 LD03283 LD03284 FIG 25 DETAIL A see pages 56 57 7 ...
Страница 69: ...69 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR TERMINAL BOX LD03233 FIG 29 COMPRESSOR TERMINAL BOXES 7 ...
Страница 70: ...70 YORK INTERNATIONAL FORM 201 18 NM1 102 Technical Data FIG 30 DETAIL B LD03285 ...
Страница 95: ...95 YORK INTERNATIONAL FORM 201 18 NM1 102 COMPRESSOR COMPONENTS CONT D FIG 43 COMPRESSOR COMPONENTS LD03670 7 ...
Страница 166: ...166 YORK INTERNATIONAL FORM 201 18 NM1 102 ...
Страница 167: ...167 YORK INTERNATIONAL FORM 201 18 NM1 102 ...