background image

JOHNSON CONTROLS

16

FORM 160.00-O1 (1020)

VSD ADAPTIVE CAPACITY CONTROL

The new York VSD utilizes a different approach to speed 

reduction compared to earlier variable speed products. 

There is no pre-programmed surge map - our adaptive 

system experiments with the speed and vanes to find 

the optimum speed for any given condition. It does not 

always encounter a “Surge” in the process, but when it 

does, the ACC stores into memory, the conditions sur-

rounding the Surge, and therefore remembers to avoid 

the stored operating point anytime in the future. This 

sounds a bit mysterious, but the process is really quite 

simple. Once you have an understanding of the steps 

involved, you will be able to watch the chiller adjust itself 

to different conditions, and understand exactly why it is 

performing in the manner it does.

Upon startup the chiller will always go to full speed. This 

is different compared to earlier systems which could go 

to a reduced speed if the total head across the chiller 

was low enough. With the VSD, the chiller will always 

run at fixed speed until two conditions are met. These 

two conditions are:

 

Achieve Setpoint 

- The leaving water temp must 

be 0.3 to -0.6 of a degree from setpoint. 

Speed reduction will not occur until the leaving water 

reaches setpoint.

 

Achieve Stability 

- The leaving water temp must 

be stable, with the vanes not driving open or closed 

to maintain the temperature at this point. Lack of 

stability will be evidenced by the vanes hunting, the 

leaving water temperature varying, and the green 

LED on the ACC board will be on, to indicate insta-

bility.

Once the above conditions are met, the ACC begins to 

lower the speed 1/10 of a hertz at a time. As the ACC 

lowers the speed, the leaving water temperature will 

begin to creep up, due to the reduction in speed. As this 

occurs, you will see the vanes begin to open slightly, just 

enough to keep the leaving water temperature within the 

setpoint window. The ACC will continue to lower speed, 

with the leaving water temperature in turn driving the 

vanes to a more open position. This process will continue 

until one of three situations occur:

 

Vanes Full Open - 

Once

 

the vanes reach the full 

open position, the ACC knows it can no longer 

reduce speed. The ACC will maintain operation at 

this point, with the vanes full-open, and the speed 

at the last point reached when the vanes hit 100%. 

If there is an increase in load while at this point, 

the ACC will increase speed until the vanes are at 

95%. The ACC will then be allowed to continue to 

optimize the speed and vanes.

 

Surge is Detected 

- If in the process of dropping 

speed and opening vanes the compressor should 

surge, the ACC will boost the speed back up enough 

to get the chiller out of surge, and will store in 

memory the head and flow conditions present at 

the time of the surge. The chiller will then know not 

to reduce speed this low again, should the same 

head and flow conditions be encountered again in 

the future. As the chiller encounters more head and 

flow combinations which result in surge, it will store 

more points, and eventually this plotting of points 

creates a “Surge Map”. Surges may be detected in 

two  ways,  by  monitoring  the  pressure  differential 

across the compressor, or by monitoring the com-

pressor motor current. Either detection will light the 

Red LED on the ACC board, indicating a surge was 

detected. The chiller may surge 6 to 8 times before 

the ACC can raise the speed enough to get the 

chiller back out of surge. Each surge is counted on 

the surge accumulator, which may be called up on 

the panel display. This surge counter will always dis-

play the total number of surges encountered by the 

chiller, not the total number of surge points. Surging 

which occurs at fixed speed will increment the surge 

counter as well. We know of one chiller which ran 

in continuous surge for two weeks due to a cooling 

tower problem. The customer’s fixed speed chiller 

was surging continuously for 2 weeks also. During 

this time, the VSD surge counter accumulated over 

18,000 surges.

 

Instability is Encountered - 

The ACC

 

may begin 

the process of reducing speed and opening the 

vanes, but may stop speed reduction prematurely 

if instability is encountered. This is the same insta-

bility discussed as one of the two conditions which 

must be met to begin reducing speed initially (See 

“Achieve Stability” above). Once the system again 

becomes unstable, no additional speed reduction 

can occur. The most common causes of instability 

are:

 

•  Valves on air-handler coils causing rapid 

changes in heat-load.

 

•  Extremely short chilled water loop.

 

•  Parallel chiller with poor control is causing 

temperature variations.

If you experience a problem with a VSD not reducing 

speed at all, make certain the system is not in manual 

speed control, and locked into fixed speed. Refer to the 

section on “Manual Speed Control” in the “Frequently 

Asked Questions” section in Form 160.00-M1. Also, 

Содержание MILLENIUM 351-46

Страница 1: ...T YK chillers furnished with an optional Variable Speed Drive VSD TABLE OF CONTENTS VSD Style Variations 2 VSD Unit and Harmonic Filter Component Overview 2 VSD Control System Overview 7 Control Panel...

Страница 2: ...cument and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question S...

Страница 3: ...any work on the chiller REVISION NOTES Revisions made to this document are indicated in the following table These revisions are to technical information and any other changes in spelling grammar or f...

Страница 4: ...er section a three phase DC to AC inverter section and an output suppression network The AC to DC rectifier utilizes a semi converter formed by the connection of three SCR diode modules 1SCR 3SCR in a...

Страница 5: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 5 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 00 O1 1020...

Страница 7: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 7...

Страница 8: ...sink temperature is also monitored using thermistor temperature sensor RT4 The Bus Isolator board 031 01624 utilizes three resistors on the board to provide a safe impedance between the DC link filter...

Страница 9: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 9 FIG 3A VSD INPUT CURRENT WITHOUT FILTER FIG 3B VSD INPUT CURRENT WITH FILTER LD02727 LD02726...

Страница 10: ...capacitors located on the phase bank assembly and the Filter logic board It provides the means to sense the positive midpoint and negative connection points of the filter s DC link VSD CONTROL SYSTEM...

Страница 11: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O1 1020 FIG 4 IEEE 519 FILTER OPTION...

Страница 13: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 13 LD02725...

Страница 14: ...f the VSD s cooling fans and pumps control of the pre charge contactor control of the semi converter gating and generation of the PWM firing pulses which are sent to the VSD gate driver and ultimately...

Страница 15: ...tz When the Filter is present these additional lines are available by scrolling INPUT KVA ___ TOTAL PWR FACTOR ____ INPUT V AB ___V BC ___V CA ___V INPUT CURR A ___A B ___A C ___A INPUT V THD A ___ B...

Страница 16: ...the vanes hit 100 If there is an increase in load while at this point the ACC will increase speed until the vanes are at 95 The ACC will then be allowed to continue to optimize the speed and vanes Su...

Страница 17: ...cur rent exceeds a given limit The motor current is sensed by the Current Transformers on the VSD output pole assemblies and the signals are sent to the VSD logic board for processing Maximum instant...

Страница 18: ...apacitors are wired in series to achieve a 900 VDC capability for the DC link It is important that the voltage be shared equally from the junction of the center or series capacitor con nection to the...

Страница 19: ...two microprocessors on the VSD logic board Message RUN RELAY FAULT Redundant run signals are generated by the Micropanel one via wire 24 and the second via the serial communica tions link Upon receip...

Страница 20: ...particular shutdown and its accompany ing message is generated if the filter s DC link voltage drops to a level less than 60 VDC below the filter DC link voltage setpoint The filter DC link voltage se...

Страница 21: ...DD level of 8 or less for the VSD system Astandard VSD less the optional filter typically has an input current TDD level on the order of 28 30 Message WARNING FILTER DATA LOSS This message is displaye...

Страница 22: ...age was intended as a check of the 519 logic board s internal triangle waveform generator However the accuracy of the measuring circuit on the board can have as much error as the generator it is tryin...

Страница 23: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 23 NOTES...

Страница 24: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O1 1020 Issue Date Octob...

Отзывы: