FORM 160.00-O1 (1020)

JOHNSON CONTROLS

15

Style “B” Units – 

For the first time, we have imple

-

mented a system which records real-time data, even if 

the chiller is not running.  Since four power losses, or 

four unsuccessful attempts at starting would overwrite 

data from the last time the chiller ran, specific history 

displays have been generated as follows:

  CURRENT OR LAST SYSTEM RUN DATA
  LAST SFTY / CYCL SHUTDOWN WHILE RUNNING
  SFTY / CYCL SHUTDOWN HISTORY (1)
  SFTY / CYCL SHUTDOWN HISTORY (2)

The above lines appear sequentially when the VSD 

History Key is depressed.  When this key is released, 

the message being viewed at that time is maintained.  

Using the white “Advance Day / Scroll” key, the Display 

Status Message may be viewed, and by continuing to 

depress the white “Advance Day / Scroll” key, all VSD 

operating data from that instant in time may be viewed.  

For example, by depressing the VSD History key once, 

you will see:

  CURRENT OR LAST SYSTEM RUN DATA

Now by depressing the white “Advance Day / Scroll” 

key, you might see:

  21 OCT   0804    NO MALFUNCTION DETECTED

Depressing the white “Advance Day / Scroll” key again 

will display the first line of historical data.  Continue to 

depress the white key to view all lines of data.

“Hidden” Key – 

There is an unmarked button on the 

face of the control panel membrane keypad, located just 

below the “Clock” key.  When this button is pressed, you 

will see a display of four parameters:

DPP = X.XX;  PRV = XXX%;  LWTD = XX.X;  FQ = XX HZ

•  D-P/P,  the ratio of the condenser pressure minus the 

evaporator pressure  to the evaporator pressure.

•  Percent Vane Position. 100% is wide open vanes.

•  Delta T,  the  difference  between  the  leaving  water 

temperature setpoint and actual leaving water tem-

perature.

•  Output frequency in hertz.

When the Filter is present, these additional lines are 

available by scrolling:

  INPUT KVA = ___;   TOTAL PWR FACTOR = ____
  INPUT V   AB=___V.;   BC=___V.;   CA=___V.
  INPUT CURR   A=___A.;   B=___A.;   C=___A.
  INPUT V THD:   A=___%;   B=___%;   C=___%
  INPUT CURR TDD%:   A=___%;   B=___%;   C=___%

Display Data Key – 

This key functions as normal, but 

offers two additional lines of display with VSD opera

-

tion.  After scrolling through the normal displays, these 

additional lines are displayed:

  D-P/P= ___ ;  PRV POS = ___%;   FREQ = ___HZ
  TOTAL ACC SURGE COUNTS = ________

VSD History Key – 

This key provides four historical 

records.  Its exact operation varies, depending on the 

style level of the VSD and software.  The two types of 

operation are as follows:

Original and Style “A” Units – 

Four previous safety / 

cycling messages are stored, listing the message, and 

indicating the historical order by placing the history num-

ber, one through four, in parenthesis after the message.  

Using the white key labeled, “Advance Day / Scroll”, 

one can view the same lines of data as are available 

by pressing the “Options” and “VSD Parameters” keys.  

The data displayed will be that recorded at shutdown, 

if running -  or will be data from the last time the chiller 

ran, if the message was generated while the chiller was 

idle.  The recording of data from the last time the chiller 

ran, is consistent with history data records on all previ-

ous YORK micropanel designs.  Below is an example 

of four histories:

22  OCT  1501  SERIAL RECEIVE FAULT 

(1)

21  OCT  1635  SYSTEM CYCLING - AUTOSTART 

(2)

20  OCT  1000  SYSTEM CYCLING - AUTOSTART 

(3)

20  OCT  0808  SYSTEM CYCLING - AUTOSTART 

(4)

These displays will appear sequentially while depress-

ing the VSD History key.  When the VSD History key is 

released, the message present at that time is maintained 

on the screen.  With any one of these messages on the 

screen, the associated VSD operating data just prior to 

unit shutdown may be viewed by scrolling, using the 

white “Advance Day / Scroll” key.

Содержание MILLENIUM 351-46

Страница 1: ...T YK chillers furnished with an optional Variable Speed Drive VSD TABLE OF CONTENTS VSD Style Variations 2 VSD Unit and Harmonic Filter Component Overview 2 VSD Control System Overview 7 Control Panel...

Страница 2: ...cument and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question S...

Страница 3: ...any work on the chiller REVISION NOTES Revisions made to this document are indicated in the following table These revisions are to technical information and any other changes in spelling grammar or f...

Страница 4: ...er section a three phase DC to AC inverter section and an output suppression network The AC to DC rectifier utilizes a semi converter formed by the connection of three SCR diode modules 1SCR 3SCR in a...

Страница 5: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 5 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 00 O1 1020...

Страница 7: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 7...

Страница 8: ...sink temperature is also monitored using thermistor temperature sensor RT4 The Bus Isolator board 031 01624 utilizes three resistors on the board to provide a safe impedance between the DC link filter...

Страница 9: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 9 FIG 3A VSD INPUT CURRENT WITHOUT FILTER FIG 3B VSD INPUT CURRENT WITH FILTER LD02727 LD02726...

Страница 10: ...capacitors located on the phase bank assembly and the Filter logic board It provides the means to sense the positive midpoint and negative connection points of the filter s DC link VSD CONTROL SYSTEM...

Страница 11: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 11 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...JOHNSON CONTROLS 12 FORM 160 00 O1 1020 FIG 4 IEEE 519 FILTER OPTION...

Страница 13: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 13 LD02725...

Страница 14: ...f the VSD s cooling fans and pumps control of the pre charge contactor control of the semi converter gating and generation of the PWM firing pulses which are sent to the VSD gate driver and ultimately...

Страница 15: ...tz When the Filter is present these additional lines are available by scrolling INPUT KVA ___ TOTAL PWR FACTOR ____ INPUT V AB ___V BC ___V CA ___V INPUT CURR A ___A B ___A C ___A INPUT V THD A ___ B...

Страница 16: ...the vanes hit 100 If there is an increase in load while at this point the ACC will increase speed until the vanes are at 95 The ACC will then be allowed to continue to optimize the speed and vanes Su...

Страница 17: ...cur rent exceeds a given limit The motor current is sensed by the Current Transformers on the VSD output pole assemblies and the signals are sent to the VSD logic board for processing Maximum instant...

Страница 18: ...apacitors are wired in series to achieve a 900 VDC capability for the DC link It is important that the voltage be shared equally from the junction of the center or series capacitor con nection to the...

Страница 19: ...two microprocessors on the VSD logic board Message RUN RELAY FAULT Redundant run signals are generated by the Micropanel one via wire 24 and the second via the serial communica tions link Upon receip...

Страница 20: ...particular shutdown and its accompany ing message is generated if the filter s DC link voltage drops to a level less than 60 VDC below the filter DC link voltage setpoint The filter DC link voltage se...

Страница 21: ...DD level of 8 or less for the VSD system Astandard VSD less the optional filter typically has an input current TDD level on the order of 28 30 Message WARNING FILTER DATA LOSS This message is displaye...

Страница 22: ...age was intended as a check of the 519 logic board s internal triangle waveform generator However the accuracy of the measuring circuit on the board can have as much error as the generator it is tryin...

Страница 23: ...FORM 160 00 O1 1020 JOHNSON CONTROLS 23 NOTES...

Страница 24: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 00 O1 1020 Issue Date Octob...

Отзывы: