9

AUTO

1

°C

0h 2

4

6

8

10 12 14 16 18 20 22 24

AUTO
PROG

If the 

 key is pressed and held for over 1 second, the

unoccupied mode will be accessed. If no other change is made
in this mode, the unoccupied status will remain indefinitely. If
the 

PROG

 key is pressed, the 

 icon appears, the set point

disappears and No. 0 is displayed in its place, indicating the
number of days the unoccupied status should last. Keys 
and 

 increase and decrease this number of days (with a

maximum of 99). If a number greater than 0 is programmed,
and while remaining in the unoccupied mode, the 

 icon will

flash to indicate this is temporary. Once the unoccupied sta-
tus is concluded, the thermostat will change occupation to
Day; or if the air conditioning mode is AUTO PROG, this oc-
cupation will depend upon the time schedule profile. If zero is
programmed in the unoccupied mode, it will remain indefi-
nitely.
If the air conditioning mode is AUTO PROG and there is a
temporary set point setting, or a temporary fan mode (the 
flashes), upon changing the occupation status the programmed
values are recovered and the icon stops flashing.
In the Programming Mode this   key allows selecting the
following option on the option list and to move forward through
the time schedule profile when programming same.

Fan mode key

It has the symbol 

 printed on the key itself, and the 

symbol, related to the Programming Mode, printed on the plas-
tic next to it.
Pressing this 

 key accesses the Setting Mode, which

lasts 5 seconds. In this mode the fan flashes and the pro-
grammed speed is displayed, and whether in auto or perma-
nent mode. When pressed a first time, the present status does
not change, but same is displayed only. Pressing this 
key repeatedly moves you through the speeds, indicated by
the number of wind icons displayed, and the permanent (ON)
or automatic (the word AUTO appears beneath the fan) modes.
Pressing this 

 key in the AUTO PROG air conditioning

mode changes the fan configuration as described above, but
when an occupation change is made the programmed values
of the programming menu are re-established.

In the Programming Mode this 

 allows validating the

changes made.

Outdoor temperature key

It has the symbol 

 printed on the key itself, and the 

symbol, related to the Programming Mode, printed on the plas-
tic next to it.
Pressing this key in Normal Mode displays the outdoor tem-
perature for 5 seconds.
If pressed and held for 10 seconds, the default system con-
figuration values are re-established:
OFF Mode.
Day Occupation.
Set points:
- Cool set point in Unoccupied mode 30° C.
- Cool set point in Night mode 27° C.
- Cool set point in Day mode 24° C.
- Heat set point in Day mode 21° C.
- Heat set point in Night mode 18° C.
- Heat set point in Unoccupied mode 15° C.
AUTO Fan, in automatic.
Origin of the temperature, internal probe.
Cancellation of the temperature probes offsets.
NORMAL temperature control.
Profiles programmed for each day of the week, P1.
In the Programming Mode the 

 key allows cancelling

changes made and access the previous menu level.

Programming menu

If the 

PROG

 key is pressed in Normal Mode, only the icons of

the different parameters that can be programmed are displayed
on screen:
-

Clock setting (day of the week, hours and minutes).

-

Fan program.

-

0h 2

4

6

8

10 12 14 16 18 20 22 24

Selection of time schedule profiles.

A single time schedule profile accepts the Comfort and
Economy
 (Day and Night) modes only. If pin 2 of the
micro-switch is set to OFF, this option is not displayed.

-

Set point temperature program for heat and cool in
Occupied Mode, also called Comfort or Day.

-

Set point temperature program for heat and cool in
Stand-by Mode, also called Economy or Night.

-

Set point temperature program for heat and cool in
Unoccupied Mode.

The active or selectable option will flash. The initial option is
setting the clock.

0h 2

4

6

8

10 12 14 16 18 20 22 24

When a status is changed in the time schedule profile, the
occupation status will go back to the status programmed in
the profile (without flashing), and the 

 icon will disappear.

Содержание DPC-1

Страница 1: ...ERTIFIED PERFORMANCE CGM 97 013 ACCORDING TO ISO 14001 STANDARDS ER 0028 1991 ACCORDING TO ISO 9001 STANDARDS Ref Y R70110 0306 Clima Roca York S L is participating in the EUROVENT Certification Program Products are as listed in the EUROVENT Directory of Certified Products in the program AC1 AC2 AC3 LCP and FC ...

Страница 2: ......

Страница 3: ...ng economy temperture set point stand by or night 11 Page Programming unoccupied temperature set points 12 Thermostat in unoccupied mode 12 Menu of supervising program 12 Programming calibrations of temperature readings 12 Programming origin of temperature readings 13 Programming operating mode of the temperature control 13 Activation and deactivation of communication error readout 13 Selection of...

Страница 4: ......

Страница 5: ...1 2 3 4 5 6 7 C F RH 0h 2 4 6 8 10 12 14 16 18 20 22 24 Cool Heat Unoccupied Economy night Comfort day Air conditioning mode Fan Day of the week Time Time schedule profile Timer active Temperature setting Room temperature Dead battery Relative humidity Keys locked Failure or incident Outdoor temperature Dirty filters AUTO AUTO 4 C 0h 2 4 6 8 10 12 14 16 18 20 22 24 PROG AUTO AUTO 4 C 0h 2 4 6 8 10...

Страница 6: ...r Unoccupied fan status day of the week and time COOL AUTO 5 C HEAT AUTO 5 C A demand is generated when the room temperature is below the programmed set point Set point is understood as the tem perature we want in the room Auto This mode activates heating as well as cooling operations The screen displays room temperature the word AUTO air conditioning mode the and icons flashing if there is a dema...

Страница 7: ... above 3 C the speed is HIGH Fan configuration can be carried out in two different ways By means of the programming menu Pressing the key The programming menu configures the fan for each occupa tion status occupied comfort or day stand by economy or night and unoccupied This program will be detailed further below Pressing the key gives access to the Setting mode that lasts 5 seconds Pressing the k...

Страница 8: ...to the heat and cool modes of the three occu pation modes Day Night and Unoccupied These set points must follow a descending order 1 Cool set point in Unoccupied mode 2 Cool set point in Night mode 3 Cool set point in Day mode 4 Heat set point in Day mode 5 Heat set point in Night mode 6 Heat set point in Unoccupied mode There should be a 1 difference between two consecutive set points If when mov...

Страница 9: ...air conditioning mode changes the fan configuration as described above but when an occupation change is made the programmed values of the programming menu are re established In the Programming Mode this allows validating the changes made Outdoor temperature key It has the symbol printed on the key itself and the symbol related to the Programming Mode printed on the plas tic next to it Pressing thi...

Страница 10: ...three predefined profiles P1 to P3 three addi tional user programmable profiles to and 6 pro files P7 to P12 that can be programmed through communi cation of the thermostat with the PC Upon selecting the 0h 2 4 6 8 10 12 14 16 18 20 22 24 option on the pro gramming menu all days of the week are displayed on screen with day 1 of the week Monday flashing the program pres ently memorized for this day...

Страница 11: ...ight Memorizes the programmed time schedule profile and goes back to Selection of time schedule profiles back within the same day it was left Goes on to Selection of time schedule profiles back without saving PROG Pressing and holding allows recovering the factory programmed default values and save these values Programming comfort temperature set points Occupation or Day Upon selecting the option ...

Страница 12: ...rogramming Menu back without sav ing PROG Pressing and holding allows recovering the factory programmed Unoccupied default values Thermostat in unoccupied mode In any air conditioning mode excluding the OFF mode press ing the key for 1 second accesses the Setting Mode and thermostat occupation is changed to Unoccupied If no other action is carried out the unoccupied mode re mains indefinitely If t...

Страница 13: ...is selected If S4 is selected and gives an error S3 is selected If S5 and S6 and S7 and S8 are selected goes on to S4 is no digital remote probe is in operation On the other hand when probes S3 or S4 are used and in Day mode 1 minute fan operation is activated every 15 min utes unless in the OFF mode This is carried out to keep the duct temperature equal to the room temperature The active keys are...

Страница 14: ... nal Both microswitches of the digital probe must be se lected in ON position In this case the maximum number of digital remote probes will be three The active keys are Allow changing the selected mode Memorizes selected value and goes back to the user programming menu Cancels changes made and goes back to user pro gramming menu X1 X2 RS1 RS2 RS3 AL R B G Y Y2 O B W REAR OF FRONT PANEL THERMOSTAT ...

Страница 15: ...re origin selected is invalid 92 indoor temperature sensor not calibrated 93 communication alarm 94 Failure with terminal AL connected 95 99 Digital probe not detected When an alarm is generated the wrench icon is displayed If the error is machine or communication this icon flashes if not it remains static Filters If the dirty filters icon is displayed flashing the filters need to be changed Desig...

Страница 16: ...lation be carried out by a qualified contractor Location To assure adequate operation this thermostat should be in stalled on an indoor wall in a frequently occupied area of the building Furthermore it should be at at least 46 cms from any outdoor wall and at approximately 1 5 m above floor level in an area with free air flow and at an average tempera ture The following locations should be avoided...

Страница 17: ... The remaining 7 cables are neces sary if a thermostat is to be used with relays with connec tions G Y1 Y2 O B W To connect the remote sensor connection a shielded 2 x 0 5 mm2 cable with a maximum length of 100 m should be used between the thermostat and the sensor The connec tions to be made are RS1 and RS2 For digital remote probe connection use shielded 3 x 0 5 mm cable with a maximum length of...

Страница 18: ... 45 122 43 041 41 068 39 196 37 419 35 733 34 132 32 612 31 167 29 795 28 490 27 250 26 070 24 947 23 880 22 863 21 895 20 974 20 096 19 259 18 462 17 702 16 978 16 287 15 627 14 998 14 398 13 824 13 277 12 754 12 254 11 777 11 321 10 884 10 467 10 068 9 686 9 321 8 971 8 636 8 316 8 009 7 715 7 433 7 163 6 904 6 656 6 418 6 189 5 970 5 760 Current 0 445 0 464 0 483 0 503 0 523 0 544 0 566 0 587 0...

Страница 19: ...19 ...

Страница 20: ...20 ...

Отзывы: