Temperature table
The following table indicates the ratio between the tempera-
ture, heater and voltage. Ambient probe 15 K Ohm: Thermo-
All data subject to change without notice.
stats DPC-1 and DPC-1R, ambient remote probe (RS-1), ducts
remote probe (DS-1) and average probe (AS-1).
Temperature °C
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
NTC value
57 382
54 657
52 077
49 633
47 317
45 122
43 041
41 068
39 196
37 419
35 733
34 132
32 612
31 167
29 795
28 490
27 250
26 070
24 947
23 880
22 863
21 895
20 974
20 096
19 259
18 462
17 702
16 978
16 287
15 627
14 998
14 398
13 824
13 277
12 754
12 254
11 777
11 321
10 884
10 467
10 068
9 686
9 321
8 971
8 636
8 316
8 009
7 715
7 433
7 163
6 904
6 656
6 418
6 189
5 970
5 760
Current
0.445
0.464
0.483
0.503
0.523
0.544
0.566
0.587
0.610
0.633
0.656
0.680
0.704
0.729
0.754
0.779
0.805
0.832
0.858
0.885
0.913
0.941
0.969
0.997
1.025
1.054
1.083
1.112
1.141
1.171
1.200
1.230
1.259
1.289
1.318
1.348
1.378
1.407
1.436
1.466
1.495
1.524
1.553
1.581
1.610
1.638
1.666
1.694
1.721
1.748
1.775
1.801
1.827
1.853
1.878
1.904