8

Key functions

Programming key

The word 

PROG

 is printed on this key.

In the Normal Mode and by pressing this key, the Program-
ming Mode is accessed, allowing the selection of one of the
following options:
-

Clock setting (day of the week, hours and minutes).

-

Fan programming.

-

0h 2

4

6

8

10 12 14 16 18 20 22 24

Time schedule profile programming.

A time schedule profile accepts Comfort and Economy
(Day and Night)
 modes only.

-

Programming of set point temperatures for heat and
cool in Occupied, Comfort or Day Modes.

-

Programming of set point temperatures for heat and
cool in Stand-by, Economy or Night Modes.

-

Programming of set point temperatures for heat and
cool in Unoccupied Mode.

Also used to define the number of days the thermostat will
remain off.

Plus and minus keys

These are 

 and 

.

Pressing one of these two keys in Normal Mode accesses
the Setting Mode, displaying present temperature set point,
with the   icon flashing (as long as the unit is not in OFF
mode).
If pressed and held for over 1 second, or released and pressed
again while still in the Setting Mode, said set point will be
increased or decreased in steps of 0.5° C or 1° F.
If in AUTO PROG MODE 

 icon will appear flashing, indi-

cating set point change is temporary. This change will remain
valid until a change is made in the occupation of the time
schedule profile. When this change in the time schedule pro-
file is made, the programmed set points are restored. Also, if
a change is made in the occupation status mode (Day/Night),
the programmed set point is re-established.
In the remaining air conditioning modes these changes are
made on the programmed set point values by means of the
programming menu.

AUTO

3

°C

0h 2

4

6

8

10 12 14 16 18 20 22 24

AUTO
PROG

If the thermostat is in the AUTO or AUTO PROG mode, in the
Setting Mode one of the heat or cool icons only will appear. If
the Setting Mode is accessed with the 

 key, the heat

set point is displayed; if entered with the 

 key, the cool

set point. Once in the Setting Mode, the set point of the mode
not displayed (from cool to heat or vice versa) can be changed
by pressing the 

MODE

 key.

There is a total of six programmable temperature set points
that correspond to the heat and cool modes of the three occu-
pation modes (Day, Night and Unoccupied). These set points
must follow a descending order:
1. Cool set point in Unoccupied mode.
2. Cool set point in Night mode.
3. Cool set point in Day mode.
4. Heat set point in Day mode.
5. Heat set point in Night mode.
6. Heat set point in Unoccupied mode.
There should be a 1° difference between two consecutive set
points. If when moving one of the set points we come to less
than one degree centigrade from the following set point, it will
be "dragged" so as to avoid the unsuitability of the set points.
When this happens, the thermostat will flash the icon of the
occupation mode of this set point. Upon exiting the Setting
Mode
 these flashes and icons of the dragged set points dis-
appear.
If while in the Normal or Setting Mode both 

 and 

keys are pressed simultaneously, the temperature reading goes
from °C to °F, and vice versa.
In the Programming Mode these keys allow changing the value
of the selected parameters.

Air conditioning mode key

It has the word 

MODE

 printed on the key itself, and the 

symbol, related to the Programming Mode, printed on the plas-
tic over it.
Pressing this key in Normal Mode leads to the Setting Mode,
changing the present air conditioning mode (OFF, COOL,
HEAT, AUTO, AUTO PROG, EMERG HEAT). After pressing
this key the air conditioning mode will be displayed and flash
for 5 seconds, indicating the change, and then go back to the
Normal Mode.
In the Programming Mode  , this key allows selecting the
previous option on the option list and move backwards through
the time schedule profile when programming same.

Occupation mode key

It has the symbol 

 printed on the key itself, and the 

symbol, related to the Programming Mode, printed on the plas-
tic next to it.
Pressing this key in Normal Mode leads to the Setting Mode,
changing the present occupation or comfort mode (Day/Night)
and displaying the set point temperature next to the flashing
thermometer. If pressed once again while still in the Setting
Mode
, each occupation mode will be accessed one by one in
a sequential and cyclic manner.
If while in the AUTO PROG (time schedule profile) mode the
occupation mode is changed and same does not coincide
with the mode programmed in the time schedule profile, the
icon of the selected mode will be displayed flashing, along
with the 

 icon, also flashing, indicating this is temporary.

Содержание DPC-1

Страница 1: ...ERTIFIED PERFORMANCE CGM 97 013 ACCORDING TO ISO 14001 STANDARDS ER 0028 1991 ACCORDING TO ISO 9001 STANDARDS Ref Y R70110 0306 Clima Roca York S L is participating in the EUROVENT Certification Program Products are as listed in the EUROVENT Directory of Certified Products in the program AC1 AC2 AC3 LCP and FC ...

Страница 2: ......

Страница 3: ...ng economy temperture set point stand by or night 11 Page Programming unoccupied temperature set points 12 Thermostat in unoccupied mode 12 Menu of supervising program 12 Programming calibrations of temperature readings 12 Programming origin of temperature readings 13 Programming operating mode of the temperature control 13 Activation and deactivation of communication error readout 13 Selection of...

Страница 4: ......

Страница 5: ...1 2 3 4 5 6 7 C F RH 0h 2 4 6 8 10 12 14 16 18 20 22 24 Cool Heat Unoccupied Economy night Comfort day Air conditioning mode Fan Day of the week Time Time schedule profile Timer active Temperature setting Room temperature Dead battery Relative humidity Keys locked Failure or incident Outdoor temperature Dirty filters AUTO AUTO 4 C 0h 2 4 6 8 10 12 14 16 18 20 22 24 PROG AUTO AUTO 4 C 0h 2 4 6 8 10...

Страница 6: ...r Unoccupied fan status day of the week and time COOL AUTO 5 C HEAT AUTO 5 C A demand is generated when the room temperature is below the programmed set point Set point is understood as the tem perature we want in the room Auto This mode activates heating as well as cooling operations The screen displays room temperature the word AUTO air conditioning mode the and icons flashing if there is a dema...

Страница 7: ... above 3 C the speed is HIGH Fan configuration can be carried out in two different ways By means of the programming menu Pressing the key The programming menu configures the fan for each occupa tion status occupied comfort or day stand by economy or night and unoccupied This program will be detailed further below Pressing the key gives access to the Setting mode that lasts 5 seconds Pressing the k...

Страница 8: ...to the heat and cool modes of the three occu pation modes Day Night and Unoccupied These set points must follow a descending order 1 Cool set point in Unoccupied mode 2 Cool set point in Night mode 3 Cool set point in Day mode 4 Heat set point in Day mode 5 Heat set point in Night mode 6 Heat set point in Unoccupied mode There should be a 1 difference between two consecutive set points If when mov...

Страница 9: ...air conditioning mode changes the fan configuration as described above but when an occupation change is made the programmed values of the programming menu are re established In the Programming Mode this allows validating the changes made Outdoor temperature key It has the symbol printed on the key itself and the symbol related to the Programming Mode printed on the plas tic next to it Pressing thi...

Страница 10: ...three predefined profiles P1 to P3 three addi tional user programmable profiles to and 6 pro files P7 to P12 that can be programmed through communi cation of the thermostat with the PC Upon selecting the 0h 2 4 6 8 10 12 14 16 18 20 22 24 option on the pro gramming menu all days of the week are displayed on screen with day 1 of the week Monday flashing the program pres ently memorized for this day...

Страница 11: ...ight Memorizes the programmed time schedule profile and goes back to Selection of time schedule profiles back within the same day it was left Goes on to Selection of time schedule profiles back without saving PROG Pressing and holding allows recovering the factory programmed default values and save these values Programming comfort temperature set points Occupation or Day Upon selecting the option ...

Страница 12: ...rogramming Menu back without sav ing PROG Pressing and holding allows recovering the factory programmed Unoccupied default values Thermostat in unoccupied mode In any air conditioning mode excluding the OFF mode press ing the key for 1 second accesses the Setting Mode and thermostat occupation is changed to Unoccupied If no other action is carried out the unoccupied mode re mains indefinitely If t...

Страница 13: ...is selected If S4 is selected and gives an error S3 is selected If S5 and S6 and S7 and S8 are selected goes on to S4 is no digital remote probe is in operation On the other hand when probes S3 or S4 are used and in Day mode 1 minute fan operation is activated every 15 min utes unless in the OFF mode This is carried out to keep the duct temperature equal to the room temperature The active keys are...

Страница 14: ... nal Both microswitches of the digital probe must be se lected in ON position In this case the maximum number of digital remote probes will be three The active keys are Allow changing the selected mode Memorizes selected value and goes back to the user programming menu Cancels changes made and goes back to user pro gramming menu X1 X2 RS1 RS2 RS3 AL R B G Y Y2 O B W REAR OF FRONT PANEL THERMOSTAT ...

Страница 15: ...re origin selected is invalid 92 indoor temperature sensor not calibrated 93 communication alarm 94 Failure with terminal AL connected 95 99 Digital probe not detected When an alarm is generated the wrench icon is displayed If the error is machine or communication this icon flashes if not it remains static Filters If the dirty filters icon is displayed flashing the filters need to be changed Desig...

Страница 16: ...lation be carried out by a qualified contractor Location To assure adequate operation this thermostat should be in stalled on an indoor wall in a frequently occupied area of the building Furthermore it should be at at least 46 cms from any outdoor wall and at approximately 1 5 m above floor level in an area with free air flow and at an average tempera ture The following locations should be avoided...

Страница 17: ... The remaining 7 cables are neces sary if a thermostat is to be used with relays with connec tions G Y1 Y2 O B W To connect the remote sensor connection a shielded 2 x 0 5 mm2 cable with a maximum length of 100 m should be used between the thermostat and the sensor The connec tions to be made are RS1 and RS2 For digital remote probe connection use shielded 3 x 0 5 mm cable with a maximum length of...

Страница 18: ... 45 122 43 041 41 068 39 196 37 419 35 733 34 132 32 612 31 167 29 795 28 490 27 250 26 070 24 947 23 880 22 863 21 895 20 974 20 096 19 259 18 462 17 702 16 978 16 287 15 627 14 998 14 398 13 824 13 277 12 754 12 254 11 777 11 321 10 884 10 467 10 068 9 686 9 321 8 971 8 636 8 316 8 009 7 715 7 433 7 163 6 904 6 656 6 418 6 189 5 970 5 760 Current 0 445 0 464 0 483 0 503 0 523 0 544 0 566 0 587 0...

Страница 19: ...19 ...

Страница 20: ...20 ...

Отзывы: