Micro-switch SW1 allow the configuration of the following pa-
rameters:
- Pin 1: Lock keyboard. In OFF the keyboard is not locked. In

ON the keyboard is locked and the locked keyboard icon
(key) is displayed. The keys that remain active are: 

,

 and 

 (Consult outdoor temperature).

- Pin 2: AUTO PROG mode activated. Defines whether the

automatic air condition mode with time schedule program-
ming (time schedule profiles) can be activated. OFF indi-
cates the AUTO PROG mode is deactivated, and ON indi-
cates the AUTO PROG mode can be selected.

- Pin 3: O/B signal: Set to OFF, heat is generated when the

O/B (24 VAC) signal is active, and cool when inactive. Set
to ON, cool is generated when the O/B (24 VAC) signal is
active, and heat when inactive.

- Pin 4: 2 minutes/4 minutes. Defines the time between the

end of one phase and when it can be active again. OFF
indicates 2 minutes, and ON, 4 minutes.

- Pin 5: Multi-stage. Defines single-stage (one stage can be

activated only) or multi-stage (more than one can be acti-
vated). OFF indicates single-stage and ON, multi-stage. In
heat, if stage W exists, in single-stage Y1 and W are acti-
vated.

- Pin 6: Single-speed fan. Defines whether the fan can oper-

ate at one or three speeds. OFF indicates 3 speeds and
ON, 1 speed. In single-speed, the wind icons are not dis-
played.

By default, all micro-switches are set to OFF.

Default parameters

OFF Mode.
Day occupation.
Set points:
- Cool set point in Unoccupied mode 30° C.
- Cool set point in Night mode 27° C.
- Cool set point in Day mode 24° C.
- Heat set point in Day mode 21° C.
- Heat set point in Night mode 18° C.
- Heat set point in Unoccupied mode 15° C.
AUTO Fan, in automatic.
Origin of the temperature, internal probe.
Cancellation of the temperature probes offsets.
NORMAL temperature control.
Profiles programmed for each day of the week, P1.

Alarms

The alarm codes are displayed at the bottom left of the screen,
overlapping hour and minutes.
The alarm codes are as follows:
- 0-90, machine error codes.
- 91, temperature origin selected is invalid.
- 92, indoor temperature sensor not calibrated.
- 93, communication alarm.
- 94, Failure with terminal "AL" connected.
- 95-99, Digital probe not detected.
When an alarm is generated, the wrench icon is displayed. If
the error is machine or communication, this icon flashes; if
not it remains static.
Filters. If the dirty filters icon is displayed flashing, the filters
need to be changed.

Designation

Code

11 / 21 / 31

12 / 22 / 32

13 / 23 / 33

14

15 / 25 / 35

16

41

42

43

44

45

46

91

92

93

94

95

96

97

98

99

Compressor discharge temperature surpased or
short circuited probe

Indoor fan thermal switch

Repeated start-ups in cool, or suction temperature
< -25°C

Liquid temperature < -30°C

Gas 1 or electrical heater 1

Gas 2 or electrical heater 2

Electrical heater 3

Electrical heater 4

Economizer or hot water coil

Smoke detector, fire thermostat or air discharge tem-
perature probe (rooftop only) >80°C

Selected probe not valid or short circuited probe

Thermostat internal probe not calibrate

No communication between the thermostat and the main
PCB (Yklon)

Failure with terminal "AL" connected

Digital probe S5 not detected

Digital probe S6 not detected

Digital probe S7 not detected

Digital probe S8 not detected

Outdoor digital probe not detected

Dead battery. The dead battery icon indicates the batteries
are dead, and these should be changed. System configura-
tion is not lost when changing the batteries. Only day and
time are lost.

Table of failures

High Pressure switch, outdoor fan overload or com-
pressor motor protection module

Low Pressure switch

Temperature control

The purpose of this thermostat is to keep the room at the
temperature established by the set points. When operating in
AUTO or AUTO PROG, the heat and cool set points are used.
However, when operating in HEAT the heat set points are used
only, and when operating in COOL the cool set points are
used only. When the temperature between the real tempera-
ture and the set point is more than 0.2° C, the first stage Y1 is
activated. If after a while (depending upon the temperature
control operating mode TURBO, NORMAL, ECONOMY) the
temperature has not recovered, the second stage Y2 is acti-

Содержание DPC-1

Страница 1: ...ERTIFIED PERFORMANCE CGM 97 013 ACCORDING TO ISO 14001 STANDARDS ER 0028 1991 ACCORDING TO ISO 9001 STANDARDS Ref Y R70110 0306 Clima Roca York S L is participating in the EUROVENT Certification Program Products are as listed in the EUROVENT Directory of Certified Products in the program AC1 AC2 AC3 LCP and FC ...

Страница 2: ......

Страница 3: ...ng economy temperture set point stand by or night 11 Page Programming unoccupied temperature set points 12 Thermostat in unoccupied mode 12 Menu of supervising program 12 Programming calibrations of temperature readings 12 Programming origin of temperature readings 13 Programming operating mode of the temperature control 13 Activation and deactivation of communication error readout 13 Selection of...

Страница 4: ......

Страница 5: ...1 2 3 4 5 6 7 C F RH 0h 2 4 6 8 10 12 14 16 18 20 22 24 Cool Heat Unoccupied Economy night Comfort day Air conditioning mode Fan Day of the week Time Time schedule profile Timer active Temperature setting Room temperature Dead battery Relative humidity Keys locked Failure or incident Outdoor temperature Dirty filters AUTO AUTO 4 C 0h 2 4 6 8 10 12 14 16 18 20 22 24 PROG AUTO AUTO 4 C 0h 2 4 6 8 10...

Страница 6: ...r Unoccupied fan status day of the week and time COOL AUTO 5 C HEAT AUTO 5 C A demand is generated when the room temperature is below the programmed set point Set point is understood as the tem perature we want in the room Auto This mode activates heating as well as cooling operations The screen displays room temperature the word AUTO air conditioning mode the and icons flashing if there is a dema...

Страница 7: ... above 3 C the speed is HIGH Fan configuration can be carried out in two different ways By means of the programming menu Pressing the key The programming menu configures the fan for each occupa tion status occupied comfort or day stand by economy or night and unoccupied This program will be detailed further below Pressing the key gives access to the Setting mode that lasts 5 seconds Pressing the k...

Страница 8: ...to the heat and cool modes of the three occu pation modes Day Night and Unoccupied These set points must follow a descending order 1 Cool set point in Unoccupied mode 2 Cool set point in Night mode 3 Cool set point in Day mode 4 Heat set point in Day mode 5 Heat set point in Night mode 6 Heat set point in Unoccupied mode There should be a 1 difference between two consecutive set points If when mov...

Страница 9: ...air conditioning mode changes the fan configuration as described above but when an occupation change is made the programmed values of the programming menu are re established In the Programming Mode this allows validating the changes made Outdoor temperature key It has the symbol printed on the key itself and the symbol related to the Programming Mode printed on the plas tic next to it Pressing thi...

Страница 10: ...three predefined profiles P1 to P3 three addi tional user programmable profiles to and 6 pro files P7 to P12 that can be programmed through communi cation of the thermostat with the PC Upon selecting the 0h 2 4 6 8 10 12 14 16 18 20 22 24 option on the pro gramming menu all days of the week are displayed on screen with day 1 of the week Monday flashing the program pres ently memorized for this day...

Страница 11: ...ight Memorizes the programmed time schedule profile and goes back to Selection of time schedule profiles back within the same day it was left Goes on to Selection of time schedule profiles back without saving PROG Pressing and holding allows recovering the factory programmed default values and save these values Programming comfort temperature set points Occupation or Day Upon selecting the option ...

Страница 12: ...rogramming Menu back without sav ing PROG Pressing and holding allows recovering the factory programmed Unoccupied default values Thermostat in unoccupied mode In any air conditioning mode excluding the OFF mode press ing the key for 1 second accesses the Setting Mode and thermostat occupation is changed to Unoccupied If no other action is carried out the unoccupied mode re mains indefinitely If t...

Страница 13: ...is selected If S4 is selected and gives an error S3 is selected If S5 and S6 and S7 and S8 are selected goes on to S4 is no digital remote probe is in operation On the other hand when probes S3 or S4 are used and in Day mode 1 minute fan operation is activated every 15 min utes unless in the OFF mode This is carried out to keep the duct temperature equal to the room temperature The active keys are...

Страница 14: ... nal Both microswitches of the digital probe must be se lected in ON position In this case the maximum number of digital remote probes will be three The active keys are Allow changing the selected mode Memorizes selected value and goes back to the user programming menu Cancels changes made and goes back to user pro gramming menu X1 X2 RS1 RS2 RS3 AL R B G Y Y2 O B W REAR OF FRONT PANEL THERMOSTAT ...

Страница 15: ...re origin selected is invalid 92 indoor temperature sensor not calibrated 93 communication alarm 94 Failure with terminal AL connected 95 99 Digital probe not detected When an alarm is generated the wrench icon is displayed If the error is machine or communication this icon flashes if not it remains static Filters If the dirty filters icon is displayed flashing the filters need to be changed Desig...

Страница 16: ...lation be carried out by a qualified contractor Location To assure adequate operation this thermostat should be in stalled on an indoor wall in a frequently occupied area of the building Furthermore it should be at at least 46 cms from any outdoor wall and at approximately 1 5 m above floor level in an area with free air flow and at an average tempera ture The following locations should be avoided...

Страница 17: ... The remaining 7 cables are neces sary if a thermostat is to be used with relays with connec tions G Y1 Y2 O B W To connect the remote sensor connection a shielded 2 x 0 5 mm2 cable with a maximum length of 100 m should be used between the thermostat and the sensor The connec tions to be made are RS1 and RS2 For digital remote probe connection use shielded 3 x 0 5 mm cable with a maximum length of...

Страница 18: ... 45 122 43 041 41 068 39 196 37 419 35 733 34 132 32 612 31 167 29 795 28 490 27 250 26 070 24 947 23 880 22 863 21 895 20 974 20 096 19 259 18 462 17 702 16 978 16 287 15 627 14 998 14 398 13 824 13 277 12 754 12 254 11 777 11 321 10 884 10 467 10 068 9 686 9 321 8 971 8 636 8 316 8 009 7 715 7 433 7 163 6 904 6 656 6 418 6 189 5 970 5 760 Current 0 445 0 464 0 483 0 503 0 523 0 544 0 566 0 587 0...

Страница 19: ...19 ...

Страница 20: ...20 ...

Отзывы: