63
AYK550-UH User’s Manual
Start-Up
1106
REF2 SELECT
0…19
1
19
9
Selects the signal source for external reference
REF
2.
0…17 – Same as for parameter 1103
REF
1
SELECT
.
19 =
PID
1
OUT
– The reference is taken from the
PID
1 output. See Groups 40 and 41.
1107
REF2 MIN
0.0…100.0%
0.1%
0.0%
(torque: 0…600%)
Sets the minimum for external reference 2.
• The minimum analog input signal (in volts or amps) corresponds to
REF
2
MIN
in %.
• Parameter 1301
MINIMUM
AI
1 or 1304
MINIMUM
AI
2 sets the minimum analog input signal.
• This parameter sets the minimum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque
1108
REF2 MAX
0.0…100.0%
0.1%
100.0%
(torque: 0…600%)
Sets the maximum for external reference 2.
• The maximum analog input signal (in volts or amps) corresponds to
REF
2
MAX
in %.
• Parameter 1302
MAXIMUM
AI
1 or 1305
MAXIMUM
AI
2 sets the maximum analog input signal.
• This parameter sets the maximum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque
Group 11: Reference Select
Code Description Range
Resolution
Default
S
19 =
PID
1
1…17
REF
2
SELECT
LIMIT
MAX
(1107, 1108)
MIN
(1107, 1108)
PFA
If PFA is used
Содержание AYK 550
Страница 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Страница 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Страница 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...
Страница 259: ...AYK550 UH User s Manual D4 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205651 Fig 4...
Страница 260: ...D5 AYK550 UH User s Manual Appendix D Base Drive w Bypass Non Fused Disconnect Drawing 205649 Fig 5...
Страница 261: ...AYK550 UH User s Manual D6 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205653 Fig 6...
Страница 262: ...D7 AYK550 UH User s Manual Appendix D Single Point Power Base Drive w Non Fused Disconnect Drawing 205663 Fig 7...
Страница 263: ...AYK550 UH User s Manual D8 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205652 Fig 8...
Страница 264: ...D9 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 205650 Fig 9...
Страница 265: ...AYK550 UH User s Manual D10 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205654 Fig 10...
Страница 266: ...D11 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 206650 Fig 11...