AYK550-UH User’s Manual
Start-Up
Group 53: EFB Protocol
This group defines set-up variables used for an embedded fieldbus (EFB)
communication protocol. Refer to communication protocol documentation for more
information on these parameters. EFBs are internal embedded protocols selected in
Group 98.
Group 53: EFB Control
Code Description Range
Resolution
Default
S
5301
EFB PROTOCOL ID
0000…FFFF hex
1
0000 hex
Contains the identification and program revision of the protocol.
• Format: XXYY, where xx = protocol ID, and YY = program revision.
5302
EFB STATION ID
0…65535
1
1
9
Defines the node address of the RS485 link.
• The node address on eAYK unit must be unique.
5303
EFB BAUD RATE
1.2…57.6 kbits/s
-
9.6 kbits/s
Defines the communication speed of the RS485 link in kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
5304
EFB PARITY
0…3
0
Defines the data length parity and stop bits to be used with the RS485 link communication.
• The same settings must be used in all on-line stations.
0 = 8
N
1 – 8 data bits, No parity, one stop bit.
1 = 8
N
2 – 8 data bits, No parity, two stop bits.
2 = 8
E
1 – 8 data bits, Even parity, one stop bit.
3 = 8
O
1 – 8 data bits, Odd parity, one stop bit.
5305
EFB CTRL PROFILE
0, 1
1
0
Selects the communication 1=AYK550 profile used by the EFB protocol.
0 = YORK/ABB
DRIVES
– Operation of Control Word and Status Word conforms to YORK Drives Profile.
1 = AYK550 – Alternate 32 bit profile (Advanced users only).
5306
EFB OK MESSAGES
0…65535
1
0
Contains a count of valid messages received by the drive.
• During normal operation, this counter is increasing constantly.
5307
EFB CRC ERRORS
0…65535
1
0
Contains a count of the messages with a CRC error received by the drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate errors.
• CRC calculations for possible errors.
5308
EFB UART ERRORS
0…65535
1
0
Contains a count of the messages with a character error received by the drive.
5309
EFB STATUS
0…7
1
0
Contains the status of the EFB protocol.
0 =
IDLE
– EFB protocol is configured, but not receiving any messages.
1 =
EXEC
.
INIT
– EFB protocol is initializing.
2 =
TIME
OUT
– A timeout has occurred in the communication between the network master and the EFB protocol.
3 =
CONFIG
ERROR
– EFB protocol has a configuration error.
4 =
OFF
-
LINE
– EFB protocol is receiving messages that are NOT addressed to this drive.
5 =
ON
-
LINE
– EFB protocol is receiving messages that are addressed to this drive.
6 =
RESET
– EFB protocol is performing a hardware reset.
7 =
LISTEN
ONLY
– EFB protocol is in listen-only mode.
Содержание AYK 550
Страница 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Страница 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Страница 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...
Страница 259: ...AYK550 UH User s Manual D4 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205651 Fig 4...
Страница 260: ...D5 AYK550 UH User s Manual Appendix D Base Drive w Bypass Non Fused Disconnect Drawing 205649 Fig 5...
Страница 261: ...AYK550 UH User s Manual D6 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205653 Fig 6...
Страница 262: ...D7 AYK550 UH User s Manual Appendix D Single Point Power Base Drive w Non Fused Disconnect Drawing 205663 Fig 7...
Страница 263: ...AYK550 UH User s Manual D8 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205652 Fig 8...
Страница 264: ...D9 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 205650 Fig 9...
Страница 265: ...AYK550 UH User s Manual D10 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205654 Fig 10...
Страница 266: ...D11 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 206650 Fig 11...