146
AYK550-UH User’s Manual
Serial Communication – EFB
Miscellaneous Drive Control
Using the fieldbus for miscellaneous drive control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied command(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent – the
table shows samples.)
1. Applies only for Modbus using YORK Drive profile.
2. BACnet not defined at time of publication.
3. Use Memorize Point command.
Relay Output Control
Using the fieldbus for relay output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Drive Parameter
Value
Setting
Protocol Reference
Modbus
1
N2
FLN BACnet
2
1601
RUN
ENABLE
7 (
COMM
) Run enable by fieldbus.
40001
bit 3
BO4
35
1604
FAULT
RESET
SEL
8 (
COMM
) Fault reset by fieldbus.
40001
bit 7
BO6
94
1607
PARAM
SAVE
1 (
SAVE
)
Saves altered parameters
to memory (then value
returns to 0).
41607
BO18
N/A
3
Drive Parameter
Value
Setting
Protocol Reference
Modbus
2
N2
FLN BACnet
3
1401
RELAY
OUTPUT
1
35 (
COMM
) Relay Output 1
controlled by
fieldbus.
40134
bit 0 or
00033
BO7
40
1402
RELAY
OUTPUT
2
35 (
COMM
) Relay Output 2
controlled by
fieldbus.
40134
bit 1 or
00034
BO8
41
1403
RELAY
OUTPUT
3
35 (
COMM
) Relay Output 3
controlled by
fieldbus.
40134
bit 2 or
00035
BO9
42
1410
1
RELAY
OUTPUT
4
35 (
COMM
) Relay Output 4
controlled by
fieldbus.
40134
bit 3 or
00036
BO10 43
1411
1
RELAY
OUTPUT
5
35 (
COMM
) Relay Output 5
controlled by
fieldbus.
40134
bit 4 or
00037
BO11 44
1412
1
RELAY
OUTPUT
6
35 (
COMM
) Relay Output 6
controlled by
fieldbus.
40134
bit 5 or
00038
BO12 45
Содержание AYK 550
Страница 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Страница 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Страница 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...
Страница 259: ...AYK550 UH User s Manual D4 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205651 Fig 4...
Страница 260: ...D5 AYK550 UH User s Manual Appendix D Base Drive w Bypass Non Fused Disconnect Drawing 205649 Fig 5...
Страница 261: ...AYK550 UH User s Manual D6 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205653 Fig 6...
Страница 262: ...D7 AYK550 UH User s Manual Appendix D Single Point Power Base Drive w Non Fused Disconnect Drawing 205663 Fig 7...
Страница 263: ...AYK550 UH User s Manual D8 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205652 Fig 8...
Страница 264: ...D9 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 205650 Fig 9...
Страница 265: ...AYK550 UH User s Manual D10 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205654 Fig 10...
Страница 266: ...D11 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 206650 Fig 11...