Code Description Range
Resolution
Default
S
3601
TIMERS ENABLE
-6…7
1
0
Selects the source for the timer enable signal.
0 = NOT SEL – Timed functions are disabled.
1 = DI1- Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated for timed functions enable.
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the timed function enable signal.
7 = ENABLED – Timed functions are enabled.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated for timed function enable.
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the timed function enable signal.
3602
START TIME 1
00:00:00…23:59:58
2 s
12:00:00
Defines the daily start time.
• The time can be changed in steps of 2 seconds.
• If parameter value is 07:00:00, then the period will
be activated at 7 a.m.
• The figure shows multiple periods on different
weekdays.
When editing parameters to set times:
• Use arrow keys to select desired hour setting.
• Press NEXT to advance to minutes.
• Use arrow keys to select desired minutes setting.
• Press NEXT to advance to minutes.
• Use arrow keys to select desired seconds setting.
• Press SAVE.
3603
STOP TIME 1
00:00:00…23:59:58
2 s
12:00:00
Defines the daily stop time.
• The time can be changed in steps of 2 seconds.
• If the parameter value is 09:00:00, then the period will be deactivated at 9 a.m.
3604
START DAY 1
1…7
1
1
Defines the weekly start day.
1 = Monday…7 = Sunday.
• If parameter value is 1, then period 1 weekly is active from Monday midnight (00:00:00).
3605
STOP DAY 1
1…7
1
1
Defines weekly stop day.
1 = Monday…7 = Sunday.
• If parameter value is 5, then timer 1 weekly will be deactivated on Friday midnight (23:59:58).
3606
START TIME 2
00:00:00…23:59:58
2 s
12:00:00
Defines timer2 daily start time.
• See parameter 3602
3607
STOP TIME 2
00:00:00…23:59:58
2 s
12:00:00
Defines timer2 daily stop time.
• See parameter 3603
3608
START DAY 2
1…7
1
1
Defines timer 2 weekly start day.
• See parameter 3604
00:00:00
09:00:00
10:30:00
12:00:00
13:00:00
15:00:00
17:00:00
20:30:00
Mon Tue Wed Thu
Fri
Sat Sun
Содержание AYK 550
Страница 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Страница 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Страница 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...
Страница 259: ...AYK550 UH User s Manual D4 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205651 Fig 4...
Страница 260: ...D5 AYK550 UH User s Manual Appendix D Base Drive w Bypass Non Fused Disconnect Drawing 205649 Fig 5...
Страница 261: ...AYK550 UH User s Manual D6 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205653 Fig 6...
Страница 262: ...D7 AYK550 UH User s Manual Appendix D Single Point Power Base Drive w Non Fused Disconnect Drawing 205663 Fig 7...
Страница 263: ...AYK550 UH User s Manual D8 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205652 Fig 8...
Страница 264: ...D9 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 205650 Fig 9...
Страница 265: ...AYK550 UH User s Manual D10 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205654 Fig 10...
Страница 266: ...D11 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 206650 Fig 11...