AYK550-UH User’s Manual
151
Serial Communication – EFB
• 5308
EFB
UART
ERRORS
does not advance at all (advances when character format
errors are detected, such as parity or framing errors).
• 5309
EFB
status value varies depending on network traffic.
Loss of Communication
The AYK550 behavior, if communication is lost, was configured earlier in
"Communication Fault". The parameters are 3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
. The "Parameter Descriptions" section describes these parameters in
detail.
No Master Station on Line
If no master station is on line: Neither the
EFB
OK
MESSAGES
nor the errors (5307
EFB
CRC
ERRORS
and 5308
EFB
UART
ERRORS
) increase on any of the stations.
To correct:
• Check that a network master is connected and properly programmed on the
network.
• Verify that the cable is connected, and is not cut or short circuited.
Duplicate Stations
If two or more stations have duplicate numbers:
• Two or more drives cannot be addressed.
• Every time there is a read or write to one particular station, the value for 5307
EFB
CRC
ERRORS
or 5308
EFB
UART
ERRORS
advances.
To correct: Verify the station numbers of all stations. Change conflicting station
numbers.
Swapped Wires
If the communication wires are swapped (terminal A on one drive is connected to
terminal B on another):
• The value of 5306
EFB
OK
MESSAGES
does not advance.
• The values of 5307
EFB
CRC
ERRORS
and 5308
EFB
UART
ERRORS
are advancing.
To correct: Check that the RS-485 lines are not swapped.
Fault 28 – Serial 1 Err
If the drive’s control panel shows fault code 28 “
SERIAL
1
ERR
”, check for either of the
following:
• The master system is down. To correct, resolve problem with master system.
• The communication connection is bad. To correct, check communication
connection at the drive.
• The time-out selection for the drive is too short for the given installation. The
master is not polling the drive within the specified time-out delay. To correct,
increase the time set by parameter 3019
COMM
FAULT
TIME
.
Содержание AYK 550
Страница 256: ...D1 AYK550 UH User s Manual Appendix D Appendix D Base Drive Drawing 205662 Drawings Fig 1...
Страница 257: ...AYK550 UH User s Manual D2 Appendix D Base Drive w Fused Disconnect Drawing 205648 Fig 2...
Страница 258: ...D3 AYK550 UH User s Manual Appendix D Base Drive w Non Fused Disconnect Drawing 205647 Fig 3...
Страница 259: ...AYK550 UH User s Manual D4 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205651 Fig 4...
Страница 260: ...D5 AYK550 UH User s Manual Appendix D Base Drive w Bypass Non Fused Disconnect Drawing 205649 Fig 5...
Страница 261: ...AYK550 UH User s Manual D6 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205653 Fig 6...
Страница 262: ...D7 AYK550 UH User s Manual Appendix D Single Point Power Base Drive w Non Fused Disconnect Drawing 205663 Fig 7...
Страница 263: ...AYK550 UH User s Manual D8 Appendix D Base Drive w ByPass Fused Disconnect Drawing 205652 Fig 8...
Страница 264: ...D9 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 205650 Fig 9...
Страница 265: ...AYK550 UH User s Manual D10 Appendix D Single Point Power Base Drive w ByPass Non Fused Disconnect Drawing 205654 Fig 10...
Страница 266: ...D11 AYK550 UH User s Manual Appendix D Base Drive w ByPass Non Fused Disconnect Drawing 206650 Fig 11...