ARC Model
Electric power sup‐
ply V/Ph/Hz
Electric resistor
Maximum total current
of the unit (A)
Maximum circuit
breaker (K Curve) (1)
Minimum cable cross-
section (mm
2
) (2)
Power
(kW)
Stages (No.)
Current (A)
25
2
36
106
125
50
37
2
54
124
160
70
50
2
72
142
160
70
(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.
1.7 Limits of use
Model
045
060
075
090
Voltage limits
Min./Max V
342/457
ARC/ARG
Temperature of air input in indoor coil
TH °C Min./Max.
15/23
15/23
15/23
15/23
DB °C Min./Max.
20/32
20/32
20/32
20/32
Outdoor temperature (without condensa‐
tion control)
TS °C Min.
7
7
7
7
Maximum outdoor tempera‐
ture (1)
At full
load
TS °C
46
46
46
46
At partial
load
TS °C
52
52
52
52
ARH/ARD
Summer cycle
Temperature of air input in indoor coil
WB °C Min./Max.
15/23
15/23
15/23
14/23
DB °C Min./Max.
20/32
20/32
20/32
20/32
Outdoor temperature (without condensa‐
tion control)
TS °C Min.
7
7
7
7
Maximum outdoor tempera‐
ture (1)
At full
load
TS °C
46
46
46
46
At partial
load
TS °C
52
52
52
52
Winter cycle
Temperature of air input in indoor coil
DB °C Min./Max.
10/25
10/25
10/25
10/25
Outdoor temperature
DB °C Min./Max.
-10/20
-10/20
-10/20
-10/20
ARG/ARD (2)
Gas heating
Indoor temperature
TS °C Max
30
30
30
30
Outdoor temperature
DB °C Min./Max.
-15/25
-15/25
-15/25
-15/25
1. Direct sunlight on the unit should be prevented when temperatures are higher than 43ºC. If placed under some kind of protective cover, the cover should not interfere
with the flow of outdoor ventilation.
2. The gas heating units (ARG/ARD) are only appropriate for use with gas. In LPG (Liquefied Petroleum Gas, propane) installations, it must be ensured that in no case
should gasoline in liquid form reach the gas group.
DB: Dry-bulb Thermometer; TH: Wet-bulb thermometer.
1.8 Power and application data for gas ARG / ARD
Model
Heat capacity
Gas consumption m
3
/h
Temperature rise in ºC at full
power (4)
Total (LHV) (1) kW
Net kW
Natural gas (2)
L.P.G. pro‐
pane (3)
Standard
High power
Standard
High power
Standard
High power
Optional (on‐
ly standard)
Min.
Max.
045
85
100
76
90
8,6
9,8
3,6
17
33
060
85
100
76
90
8,6
9,8
3,6
17
33
075
85
100
76
90
8,6
9,8
3,6
17
33
090
85
100
76
90
8,6
9,8
3,6
17
33
(1) LHV: Lower heating value.
(2) Natural gas 2ND-H, G20, at 20 mbar and 15 ºC
(3) Propane gas, G31, at 37 mbar and 15 ºC.
(4) The air flow should be regulated so as to increase temperature within the specified limits. Units with optional high power burners should have a minimum air flow of
10000 m
3
/h.
Note: The gas units are shipped ready to operate with natural gas. A conversion kit can be used to convert them to propane gas (L.P.G.).
1
Installation manual
1.7
Limits of use
8