Models
ARH/ARD
045
060
075
090
Net (2) kW
90
100% gas consumption (2ND-
H natural gas, G20 at 20 mbar
and 15ºC) (standard)
m
3
/h
8,6
100% gas consumption (2ND-
H natural gas, G20 at 20 mbar
and 15ºC) high capacity (op‐
tional)
m
3
/h
9,8
Stages
No.
2
Compressors
Rated/start-up current
A
2x12/95
2x15/118
2x20/140
2x25/198
Type and quantity
SCROLL, 1 (TANDEM 50 % + 50 %)
Degree of protection
IP21
Refrigerant
(R-410A)
kg
14,5
19
20,5
29
Electric power supply
V / ph / Hz
400/3+N/50
Indoor fan (3)
Rated air flow
m
3
/h
8500
11500
13500
16000
Maximum static pressure with
rated flow (standard drive)
Pa
168
242
240
368
Maximum static pressure with
rated flow (optional HPD drive)
Pa
335
402
>500
>500
Maximum flow
m
3
/h
10000
13500
16000
18000
Minimum flow
m
3
/h
7000
9500
11500
13000
IP55 Motor (standard)
kW
3
4
5,5
7,5
Rated current
A
5,5
5,7
7,6
11,7
IP55 Motor (HPD optional)
kW
4
5,5
7,5
9,2/11
Rated current
A
5,7
7,6
11,7
14/17,4
Indoor coil (evaporator)
Number of elements
No.
3
4
3
4
Distance between fins
mm
2,11
2,11
1,81
1,81
Front surface
m
2
1,44
1,58
1,95
1,06 (x 2)
Air filters (G4)
Quantity per unit
No.
6
6
Dimensions
mm
470x550x48
565x594x48
Outdoor fan
Diameter / number
mm
800/1
800/2
800/2
800/2
Total rated flow
m
3
/h
15000
23000
27000
27000
Motor (IP54)
kW
1,9
1,9
1,9
1,9
Rated current
A
3,5
2x3,5
2x3,5
2x3,5
Outdoor coil (condenser)
Number of elements
No.
3
4
2
3
Distance between fins
mm
2,11
2,54
1,81
1,81
Front area
m
2
2,27
2,49
2.31 (x2)
2.31 (x2)
Net dimensions (4)
Height
mm
1316
1367
Length
mm
3180
3495
Width
mm
2337
2337
Net weight (basic unit with‐
out accessories) (4)
ARH
kg
930
985
1145
1220
ARD
kg
1040
1095
1255
1330
Electrical features of the
unit
Total rated power
kW
17
22
28
36
Total rated current
A
32
42
54
70
Total maximum power
kW
23
31
38
45
Total maximum current
A
42
56
70
83
Circuit breaker (K Curve (5)
A
50
63
80
100
Minimum cable section (6)
mm
2
10
16
25
35
(1) Data comply with Eurovent conditions, summer: indoor 27 °C TS / 19 °C TH - outdoor TS 35 °C. Winter: Indoor TS 20 °C, outdoor TS 7 °C / TH 6 °C (TS Dry-bulb
thermometer; TH Wet-bulb thermometer).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See
Indoor fan
, see on page 18
(4) Consider the additional weight of options and accessories. To do so, see
Weight options and accessories
, see on page 7 .
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Section of cables for the power supply line based on copper conductors, 105 ºC. The indicated
circuit breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall
in planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.
1
Installation manual
1.4
Technical data
6
Содержание ARC 045
Страница 1: ...ACTIVA SERIES ROOF TOP Air Conditioners Installation manual Ref N 40XXX...
Страница 2: ......
Страница 5: ...1 Installation manual...
Страница 46: ......
Страница 47: ...2 Unit installation data...
Страница 52: ......