1.4.3 Weight options and accessories
Models
045
060
075
090
Economiser
kg
65
65
73
73
Extraction fan (axial)
kg
54
54
63
63
Return fan (centrifuge)
kg
Roof-curb mounting base (fixed/adjustable)
kg
81/157
81/157
85/165
85/165
ERP adaptor for Roof Curb
kg
177
177
190
190
Electric resistor
kg
20
20
20
20
Hot water coil
kg
60
60
60
60
Fixed outdoor air intake
kg
9
9
9
9
Barometric damper
kg
20
20
20
20
Copper fin coil
ARC/ARG
indoor
19
31
44
64
outdoor
30
49
70
104
ARH/ARD
indoor
29
48
44
64
outdoor
44
64
70
104
1.5 ARC units with electric heater
ARC Model
Electric power sup‐
ply V/Ph/Hz
Electric resistor
Maximum total current
of the unit (A)
Maximum circuit
breaker (K Curve) (1)
Minimum cable cross-
section (mm
2
) (2)
Power
(kW)
Stages (No.)
Current (A)
045
400/3/50
12
1
18
32
50
10
25
2
36
38
50
10
37
2
54
60
80
25
50
2
72
78
100
35
060
400/3/50
12
1
18
42
50
10
25
2
36
42
50
10
37
2
54
60
80
25
50
2
72
78
100
35
075
400/3/50
12
1
18
54
63
16
25
2
36
54
63
16
37
2
54
62
80
25
50
2
72
80
100
35
090
400/3/50
12
1
18
70
80
25
25
2
36
70
80
25
37
2
54
70
80
25
50
2
72
84
100
35
(1) K Curve (DIN, VDE 0660-104).
(2) Based on copper conductors 105 °C.
1.6 ARH units with electric heater
ARC Model
Electric power sup‐
ply V/Ph/Hz
Electric resistor
Maximum total current
of the unit (A)
Maximum circuit
breaker (K Curve) (1)
Minimum cable cross-
section (mm
2
) (2)
Power
(kW)
Stages (No.)
Current (A)
045
400/3/50
12
1
18
50
63
16
25
2
36
68
80
25
37
2
54
86
100
35
50
2
72
104
125
50
060
400/3/50
12
1
18
60
80
25
25
2
36
78
100
35
37
2
54
96
125
50
50
2
72
114
125
50
075
400/3/50
12
1
18
72
80
25
25
2
36
90
100
35
37
2
54
108
125
50
50
2
72
126
160
70
090
400/3/50
12
1
18
88
100
35
Installation manual
1
ARC units with electric heater
1.5
7
Содержание ARC 045
Страница 1: ...ACTIVA SERIES ROOF TOP Air Conditioners Installation manual Ref N 40XXX...
Страница 2: ......
Страница 5: ...1 Installation manual...
Страница 46: ......
Страница 47: ...2 Unit installation data...
Страница 52: ......