Inspection of the gas heating section (models ARG/ARD)
Exhaust hoods installed
Inspection of compressors
Verification that direction of rotation is correct
2.2 Start-up Data
Electrical data
Rating plate
Actual
Power supply
Check specifica‐
tions in the Installa‐
tion Manual
Control voltage
Fan consumption (A)
Consumption of condenser fan 1 (A)
Consumption of condenser fan 2 (A)
Consumption of compressor 1 (A)
Consumption of compressor 2 (A)
Consumption of supply fan (A)
Electric resistor 1 (Optional)
Electric resistor 2 (Optional)
Cool and heat modes
Refrigerant circuit. Compressor 1
Mode
Value
Subcooling (min. 8 K, max. 18 K)
ºC
Liquid pressure: _____ bar
Liquid temperature: _____ ºC
Superheat (min. 4 K, max. 10 K)
ºC
Suction pressure: _____ bar
Suction temperature: _____ ºC
Complete liquid line checked in sight glass
Correct oil level checked in sight glass
Refrigerant circuit. Compressor 2
Mode
Value
Subcooling (min. 8 K, max. 18 K)
ºC
Liquid pressure: _____ bar
Liquid temperature: _____ ºC
Superheat (min. 4 K, max. 10 K)
ºC
Suction pressure: _____ bar
Suction temperature: _____ ºC
Complete liquid line checked in sight glass
Correct oil level checked in sight glass
Air flow values
m
3
/h
Design
Measured
Unit installation data
2
Start-up Data
2.2
45
Содержание ARC 045
Страница 1: ...ACTIVA SERIES ROOF TOP Air Conditioners Installation manual Ref N 40XXX...
Страница 2: ......
Страница 5: ...1 Installation manual...
Страница 46: ......
Страница 47: ...2 Unit installation data...
Страница 52: ......