FORM 160.52-O1
13
YORK INTERNATIONAL
FRI START = 05:00 AM STOP = 07:00 PM
SAT START = 05:00 AM STOP = 01:00 PM
HOL START = 00:00 AM STOP = 00:00 PM
To Display
HOLIDAY
Setpoints:
Use
HOLIDAY
setpoint key as described in the begin-
ning of this section to produce the following message:
S_ M_ T_ W_ T_ F_ S_ HOLIDAY NOTED BY *
NOTE: On the days that are designated by an *, the
chiller will automatically start and stop per the
holiday schedule established in
DAILY
SCHEDULE
setpoints.
To Display
REMOTE RESET TEMP RANGE
Setpoint:
Use
REMOTE RESET TEMP RANGE
setpoint key as
described above to produce the following message:
REMOTE RESET TEMP RANGE = 10°F
or
REMOTE RESET TEMP RANGE = 20°F
To Display
DATA LOGGER
setpoints:
Refer to YORK, Form 160.49-N2 for operation of this
key.
To Display
UNDERVOLTAGE
setpoints:
(Solid State Starter Applications Only)
Press
SSS MOTOR CURRENT/VOLTS
key in
PRO-
GRAM
mode to display the selected voltage range. One
of the following messages will be displayed.
SUPPLY VOLTAGE RANGE 380
or
SUPPLY VOLTAGE RANGE 400
or
SUPPLY VOLTAGE RANGE 415
or
SUPPLY VOLTAGE RANGE 440-480
or
SUPPLY VOLTAGE RANGE 550-600
or
SUPPLY VOLTAGE RANGE DISABLED
A special access code is required to program the Sup-
ply Voltage Range. The Supply Voltage Range is pro-
grammed at the factory and checked at system start-
up. (Note to service technician: Refer to programming
instructions in Service Instruction, Form 160.49-M2.)